§ 1-19-8.352. STORAGE OF FLAMMABLE LIQUIDS.
   The following provisions shall apply where it is proposed to store flammable liquids in excess of 60,000 gallons in the General Commercial and Highway Service Districts.
   (A)   The minimum lot size shall be 40,000 square feet.
   (B)   The flammable liquids may be stored above or under ground.
   (C)   The storage shall be located a minimum of 100 feet from any well when underground or as provided in § 1-6-50 (Wellhead Protection Ordinance), whichever is greater.
   (D)   That the containers shall comply with the setback requirements of § 1-19-7.610(J)(4).
   (E)   Shall be governed by the International Building Code 2003 as amended concerning storage tanks, and the National Fire Protection Association 30 as amended.
   (F)   Flammable liquid storage tanks shall have 100% catchment basin, or double-walled containment and a spill protection overfill alarm. This does not apply to propane or natural gas tanks.
   (G)   Shall comply with § 1-6-50 (Wellhead Protection Ordinance) at site plan approval.
(Ord. 83-14-281, 6-7-1983; Ord. 07-16-456, 5-15-2007; Ord. 08-26-502, 10-14-2008; Ord. 14-23-678, 11-13-2014)