§ 93.22 SMOKE DETECTORS REQUIRED; TYPE AND PLACEMENT.
   (A)   In order to comply with this subchapter, only ionization or photoelectric type detectors listed by a nationally recognized testing laboratory shall be installed.
   (B)   Smoke detectors shall be installed in accordance with applicable NFPA standards and the manufacturer’s recommendations. Detectors may be ceiling- or wall-mounted; provided that, they shall be mounted at a minimum of four inches and a maximum of 12 inches from the ceiling, and not closer than four inches from the point at which the ceiling and wall meet.
   (C)   Smoke detectors shall be installed as specified by the International Building Code with Kentucky Amendments and NFPA 72 National Fire Alarm Code.
(Prior Code, § 100.03) (Ord. 25-2009, passed 12-7-2009) Penalty, see § 93.99