§ 2.03 PIPE MATERIALS AND JOINTS.
   (A)   Storm sewer. The contractor may select particular pipe material for a project from the below listed table, unless otherwise specified on the plans or in the bid documents. These pipe specifications shall govern subject to anticipated loading on the pipe. Flared end sections shall be RCP for RCP pipe and CMP for CMP pipe. Flared end sections for PVC and HDPE pipe shall be HDPE or CMP.
Type
Size Limitations
Pipe Material Specifications
Joint Specification
Pipe Envelope
Use Limitations
Type
Size Limitations
Pipe Material Specifications
Joint Specification
Pipe Envelope
Use Limitations
RCP
All
ASTM C76, Class III (minimum)
ASTM C361 and C443
Class C, Type 1
None
ARCH RCP
All
ASTM C506 Class A III (minimum)
Rubber rope gasket
Class C, Type 1
None
ELLIP RCP
All
ASTM C507 Class HE II or VE II (minimum)
Rubber rope gasket
Class C, Type 1
None
CM P
All
AASHTO M36, M190 or M245
Class B, Type 3
Under driveways as culverts
N-12 or approved equivalent
4 to 10 inches
AASHTO M252
AASHTO M252
Class B, Type 3
None
N-12 or approved equivalent
12 to 48 inches
AASHTO M294
AASHTO M252
Class B, Type 3
None
A-2000 or approved equivalent
4 to 36 inches
AASHTO F949
ASTM D3212 F477
Class B, Type 3
None
 
   (B)   Sanitary sewer.
 
Type
Size Limitations
Pipe Material Specifications
Joint Specification
Pipe Envelope
Ductile Iron Pipe (DIP)
None
Pressure Class 350, ANSI A21.51
ANSI A21.11
Class C, Type 1
Polyvinyl Chloride (PVC)
4 to 6 inches
SDR 23.5
ASTM D3034
ASTM D3212 F477
Class B, Type 3
8 to 15 inches
SDR 26
ASTM D3034
ASTM D3212 F477
Class B, Type 3
Plastic Truss (ABS or PVC)
8 to 15 inches
ASTM D2680
ASTM D3212
Class B, Type 3
A-2000 (PVC)
None
ASTM F949
ASTM 3212 F477
Class B, Type 3
 
      (1)   The contractor may select particular pipe material for a project from the below listed table, unless otherwise specified on the plans or in the bid documents. These pipe specifications shall govern subject to anticipated loading on the pipe.
      (2)   Sanitary sewer pipe trench depths exceeding 20 feet, pipe material shall be ductile iron. Depth exceeding 20 feet pipe envelope shall be per manufacturer’s recommendations and as approved by the engineer.
      (3)   Sump pump discharge pipe shall be PVC D1785, SDR 35 or approved equivalent. Bedding shall be a minimum of Class B, Type 3. The minimum size for a sump pump lateral from a single property to the sump pump main line shall be four-inch diameter. The minimum size for a sump pump discharge main line shall be eight-inch diameter and sized for the number of discharge connections. Discharge pipe shall not be located in the front of the lot, if electric is located in front of the lot. Lateral connections off the main line shall be extended to the property line or easement line. The sump pump discharge pipe header shall be provided with a cleanout structure, in accordance with standard detail SD-13, every 300 feet minimum and at the end of the line. Sump pump lines shall not be blind connected to a storm sewer pipe. Sump pump services shall be marked with a four by four wooden post painted white and a three-fourths inch diameter steel rebar three-foot long driven into the ground flush with the surface next to the wooden post. New service taps on existing sump pump lines shall be constructed in accordance with Standard Detail SD-10.