§ 53.038 LAYING OF BUILDING SEWER IN RELATION TO WATER LINE.
   No building sewer shall be laid parallel to or within three feet of any bearing wall. The depth shall be sufficient to afford protection from frost. The building sewer shall be laid at uniform grade and in straight alignments insofar as possible. The changes in direction shall be made only with curved pipe and fittings which have been approved by the Commission. Whenever sewer lines, the building drain or building sewer must cross water mains or private water lines, the sewer shall be laid at such an elevation that the top of the sewer is at least 18 inches below the bottom of the water line.
(Ord. passed 3-17-1991; Ord. passed 9-12-1998)