§ 53.015 PROHIBITED DISCHARGE STANDARDS.
   (A)   General prohibitions. No user shall introduce or cause to be introduced into the POTW any pollutant or wastewater which causes pass through or interference. These general prohibitions apply to all users of the POTW, whether or not they are subject to categorical pretreatment standards or any other national, state, or local pretreatment standards or requirements.
   (B)   Specific prohibitions. No user shall introduce or cause to be introduced into the POTW the following pollutants, substances, or wastewater:
      (1)   Pollutants which create a fire or explosive hazard in the POTW, including, but not limited to, wastestreams with a closed-cup flashpoint of less than 140°F (60°C) using the test methods specified in 40 C.F.R. § 261.21;
      (2)   Wastewater having a pH less than 6.0 or more than 10.0, or otherwise causing corrosive structural damage to the POTW or equipment;
      (3)   Solid or viscous substances in amounts which will cause obstruction of the flow in the POTW resulting in interference, but in no case solids greater than one-quarter inch or 0.635 centimeter(s) (0.635 cm) in any dimension;
      (4)   Pollutants, including oxygen-demanding pollutants (BOD and the like), released in a discharge at a flow rate and/or pollutant concentration which, either singly or by interaction with other pollutants, will cause interference with the POTW;
      (5)   Wastewater having a temperature greater than 110°F (43.3°C), or which will inhibit biological activity in the treatment plant resulting in interference, but in no case, wastewater which causes the temperature at the introduction into the treatment plant to exceed 104°F (40°C);
      (6)   Petroleum oil, non-biodegradable cutting oil, or products of mineral oil origin, in amounts that will cause interference or pass through;
      (7)   Pollutants which result in the presence of toxic gases, vapors, or fumes within the POTW in a quantity that may cause acute worker health and safety problems;
      (8)   Trucked or hauled pollutants, except at discharge points designated by the Pretreatment Coordinator in accordance with § 53.039 of this chapter;
      (9)   Noxious or malodorous liquids, gases, solids, or other wastewater which, either singly or by interaction with other wastes, are sufficient to create a public nuisance or a hazard to life, or to prevent entry into the sewers for maintenance or repair;
      (10)   Wastewater which imparts color which cannot be removed by the treatment process, such as, but not limited to, dye wastes and vegetable tanning solutions, which consequently imparts color to the treatment plant’s effluent, thereby violating the city’s OPDES permit;
      (11)   Wastewater containing any radioactive wastes or isotopes except in compliance with applicable state or federal regulations;
      (12)   Storm water, surface water, ground water, artesian well water, roof runoff, subsurface drainage, unless specifically authorized by the Superintendent or IPD;
      (13)   Sledges, screens, or other residues from the pretreatment of industrial wastes;
      (14)   Medical wastes, except as specifically authorized by the IPD in an individual or general wastewater discharge permit;
      (15)   Wastewater causing, alone or in conjunction with other sources, the treatment plants effluent to fail a toxicity test;
      (16)   Detergents, surface-active agents, or other substances which may cause excessive foaming in the POTW; or
      (17)   Fats, oils, or greases of animal or vegetable origin in concentrations greater than 200 mg/l.
   (C)   Pollutants, substances, or wastewater prohibited by this section shall not be processed or stored in such a manner that they could be discharged to the POTW.
(Prior Code, § 53.010) (Ord. 1590, passed 4-14-2009) Penalty, see § 10.99