(A) Fittings used in construction of water mains within the city shall include restrainers for all PVC and ductile iron pipe.
(B) Concrete thrust blocks are permitted, but no flowable backfill is permitted.
(C) All water mains shall be installed with #12 tracer wire to facilitate the locating of these mains after they are buried.
(Prior Code, § 52.09) (Ord. 1307, passed 5-9-2000)