(A) The design and operation of the proposed facility shall meet the standards of the Office of the Arizona State Fire Marshal.
(B) The parcel or lot shall be of sufficient size to meet all parking and automobile circulation requirements set out by this chapter. Aboveground storage tanks shall not be permitted on lots or parcels not meeting current parking or circulation standards.
(C) Aboveground L.P. (liquid propane) storage tank(s) shall be a minimum of 25 feet from all property lines.
(D) Crash guards shall be installed on three-foot centers on all sides of L.P. fuel storage tank(s) consisting of six-foot lengths of six-inch Schedule 40 steel and embedded in concrete two feet deep and 12 inches around.
(E) A minimum setback or separation of 100 feet shall be maintained from the tank to the nearest residentially zoned parcel or "R" residential occupancy building as specified under the International Building Code.
(F) The maximum size L.P. storage tank shall not exceed 2,000 gallons (water capacity).
(Ord. § 549, passed 9-4-2008)