A. Amendments: The 2014 national electrical code, adopted and incorporated by reference pursuant to this chapter, is hereby amended, in relevant part, to read as set forth in this section. Subsequent section numbers used in this section refer to the like numbered sections of, or new sections added to, the 2014 national electrical code. Whenever a conflict arises between the provisions of the 2014 national electrical code and the amendments set forth in this section, the following amendments will control:
320.12 Uses Not Permitted [Armored Cable: Type AC]
Add the following: When used in projects constructed using the International Building Code (2015), individual lengths of Armored Cable: Type AC must not exceed six feet in length.
330.12 Uses Not Permitted [Metal-Clad Cable: Type MC]
Add a new (3) after 330.12(2) as follows:
(3) When used in projects constructed using the International Building Code (2015), individual lengths of Metal-Clad Cable: Type MC must not exceed six feet in length.
410.36 Means Of Support.
(A) Outlet Boxes. Outlet boxes or fittings installed as required by 314.23 and complying with the provisions of 314.27(A)(1) and 314.27(A)(2) shall be permitted to support luminaires.
(B) Suspended Ceilings. Framing members of suspended ceiling systems used to support luminaires shall be securely fastened to each other and shall be securely attached to the building structure at appropriate intervals. Luminaires shall be securely fastened to the structure above at opposite corners of the fixture housing.
B. Administration: Appendix K of the 2015 international building code shall be used to administer the 2014 national electrical code. (Ord. M-44-15, 11-16-2015; amd. Ord. M-27-21, 11-15-2021)