§ 53.118 GREASE CONTROL.
   (A)   Purpose. 
      (1)   It is the duty and responsibility of the county to prevent the excessive introduction of grease into the sewer system and the wastewater treatment plants. This policy is designed to implement and enforce the grease discharge rules of the sewerage system policy resolution.
      (2)   The intent of this policy is to ensure compliance with the Commission's pretreatment program, as contained in the sewerage system policy resolution; the rules and regulations of the United States Environmental Protection Agency and the North Carolina Department of Environment and Natural Resources; and to protect the county's infrastructure as it relates to the sanitary sewer collection and treatment system.
      (3)   The accumulation of grease within the sewer lines increases the potential to cause sewer blockages, which in turn can cause overflows, which potentially degrade the quality of local surface waters. Blockages may also cause sewer to back-up into business establishments, or homes, and can cause extensive damage. Grease can be discharged to the sewer system from several sources, including food service establishments. In order to reduce sewer blockages, food service establishments in the county area that discharge wastewater that contains grease must install and maintain a grease trap or interceptor. These establishments include any institutional food service or business that serves food or is involved in food preparation services.
      (4)   The Director reserves the right to make determinations of grease interceptor adequacy and need, based on review of all relevant information regarding grease interceptor performance, maintenance, and facility site and building plan review to require repairs to, modification, or replacement of such interceptors or traps.
   (B)   Prohibited discharge standards.
      (1)   General prohibition. No user shall contribute or cause to be contributed into the POTW, directly or indirectly, any pollutant or wastewater which causes interference or pass through. These general prohibitions apply to all users of a POTW.
      (2)   Specific prohibitions. No user shall contribute or cause to be contributed into the POTW the following pollutants, substances, or wastewater:
         (a)   Solid or viscous substances in amounts which may cause obstruction to the flow in a sewer or other interference with the operation of the POTW.
         (b)   Any substance which may cause the POTW's effluent or any other product of the POTW such as residuals, sludges, or scums, to be unsuitable for reclamation and reuse or to interfere with the reclamation process. In no case, shall a substance discharged to the POTW cause the POTW to be in noncompliance with sludge use or disposal regulation or permits issued under § 405 of the Act; the Solid Waste Disposal Act, the Clean Air Act, the Toxic Substance Control Act, or state criteria applicable to the sludge management method being used.
   (C)   Pretreatment of wastewater.
      (1)   All food service establishments shall install and maintain a grease interceptor in accordance with the grease control policy, set forth by the Commission, and on file at the county's utilities administration office.
      (2)   The transportation and/or disposal of sludges generated by pretreatment shall be subject to applicable federal, state, and local regulations. The user shall be responsible for documenting the transportation and/or disposal of all pretreatment sludges. Manifest and other documentation shall be kept for a minimum of three years and shall be made available to the Director upon request.
   (D)   Reports from users. All users not required to obtain an industrial or commercial user permit shall provide appropriate reports to the Director as the Director may require.
   (E)   Inspection and sampling. The county has the right to enter and inspect the facilities of any user to ascertain whether the purpose of this chapter is being met and all requirements are being complied with. Persons or occupants of premises where wastewater is created, discharged or suspected to be discharged, shall allow county personnel ready access at all reasonable times to all parts of the premises for the purposes of inspection, sampling, records examination and copying or the performance of any of their duties. The county shall have the right to set up on the user's property such devices as are necessary to conduct sampling, inspection, compliance monitoring and/or metering operations. Denial of the county's access to the user's premises shall be a violation of this chapter. Unreasonable delays may constitute denial of access.
   (F)   Definitions. For the purpose of this chapter, the following definitions shall apply unless the context clearly indicates or requires a different meaning.
      COUNTY. The County of Davie, North Carolina, or any duly authorized agent(s) or official(s) acting on its behalf.
      DIRECTOR. The Director of Utilities for Public Works of the county, or his or her authorized representative(s).
      FOOD SERVICE ESTABLISHMENTS. Any commercial facility discharging kitchen or food preparation wastewater including, but not limited to the following: restaurants, motels, hotels, cafeterias, hospitals, schools, nightclubs, delicatessen, meat cutting-preparation, bakeries, bagel shops, grocery stores, gas stations, and any other facility that the commission determines to need a grease interceptor by virtue of it's operation.
      GREASE. The accumulation of oils (animal or vegetable), fats, cellulose, starch, proteins, wax, lipids, or grease, whether emulsified or not, in the sanitary sewer system. These are substances that may solidify or become viscous at temperatures between 32°F and 150°F.
      GREASE INTERCEPTOR or GREASE TRAP. A device utilized to effect the separation of grease and oils in wastewater effluent from a food service establishment. Such traps or interceptors may be of the "outdoor" or underground type normally of a 1,000-gallon capacity or more, or the "under-the counter" package units, which are typically less than 100-gallon capacity. For the purpose of this definition, the words TRAP and INTERCEPTOR are used interchangeably.
      OWNER. An individual, person, firm, company, association, society, corporation, or group upon whose property the building or structure containing the food service establishment is located or will be constructed. OWNER shall also include the owner of a food service establishment who may lease the building, structure, or a portion thereof, containing the food service establishment.
      PHYSICAL PROPERTY RESTRICTIONS. A physical property restriction does not include restrictions arising from a new building owner's decision not to provide a stub-out for grease installation before a food service establishment occupies the premises.
      PLUMBING CODE. The current edition of the North Carolina Plumbing Code.
      POTW (PUBLICLY OWNED TREATMENT WORKS). A treatment works owned by the county, acting through the county. This definition includes any devices or system used in the collection, storage, treatment, recycling, and reclamation of public sewage or industrial wastes of a liquid or solid nature. It also includes sewers, pipes, and other conveyances only if they convey wastewater to the POTW treatment plant. For the purposes of this chapter, POTW shall also include any sewers that convey wastewater to the POTW from persons outside the county who are, by contract or agreement with the county, or in any other way, users of the POTW.
      SEPTAGE MANAGEMENT FIRM. A person engaged in the business of pumping, transporting, storing, treating or disposing of septage or grease.
      USER. Any person, establishment, or facility, whether inside or outside the county limits, who contributes, causes, or permits the contribution of wastewater into the POTW.
   (G)   Design, installation and maintenance of grease interceptors. 
      (1)   All new grease interceptors shall be designed and constructed in accordance with divisions (H) and (I) herein unless otherwise approved by the Director, but in no case may it be less than the North Carolina State Plumbing Code. All grease interceptor plans and specifications shall be submitted and approved by the county prior to installation.
      (2)   All grease interceptors shall be installed by a licensed North Carolina plumbing contractor and maintained by the user at the user's expense so as to be in continuously effective operation. Maintenance shall include the complete removal of all contents, including floatable materials, wastewater, sludge, and solids. Separation, decanting or back flushing of the grease interceptor or its wastes is prohibited except where classified as a restaurant that cleans its own interceptor. This applies only to those restaurants that have a grease interceptor less than 100-gallon capacity. Maintenance of grease interceptors shall be performed in accordance with the type of interceptor as required in division (K) herein.
      (3)   The user shall be responsible for the proper removal and lawful disposal of the grease interceptor waste. All waste removed from each grease interceptor should be disposed of at a facility permitted by the North Carolina Division of Solid Waste Management to receive such waste. No grease interceptor waste shall be discharged directly to the wastewater collection system or wastewater treatment facilities.
      (4)   The county may conduct mandatory inspections of every food service establishment connected to the sewer collection system once every two years, and at other times as the county deems necessary, in its discretion.
      (5)   If grease is responsible for a sewer blockage, all food service establishments upstream from the blockage will be inspected.
      (6)   The exclusive use of enzymes or biological additives as a grease degradation agent is not considered acceptable grease interceptor maintenance practice. Any user who uses these additives must apply for a variance and follow the procedures for a variance study, as set forth in division (P) to reduce the monthly maintenance requirements.
   (H)   Design and structural criteria for exterior grease interceptors. Grease interceptors shall conform to the following criteria when being designed and constructed:
      (1)   A 24-minute retention time under actual peak flow. See sizing criteria in division (I) below.
      (2)   New in-ground grease interceptors shall be no less than 1,000 gallons total capacity unless otherwise approved by the Director.
      (3)   Interior baffles to distribute flows. Will extend six inches above water line but cannot flood the inlet pipe.
      (4)   Minimum 2:1 length to width ratio.
      (5)   Low velocity flow near outlet.
      (6)   Baffle wall shall be 2/3 to 3/4 distance from inlet wall.
      (7)   Nine inches of freeboard at grease interceptor top.
      (8)   Each grease interceptor shall have inlet and outlet tees. The outlet tee shall extend 50% into the liquid depth. The inlet tee shall extend 25% into the liquid depth. Inlet and outlet tees must be plugged at the top of the sanitary tee and be a minimum of three inches in diameter.
      (9)   Access openings over the inlet, outlet, and each compartment within the grease interceptor. A minimum of 24-inches shall be the diameter of each opening. All covers shall be constructed of cast iron or equivalent traffic bearing material.
      (10)   Grease interceptors must be vented.
      (11)   In-ground grease interceptors shall receive kitchen wastes. Kitchen wastes include: pot sinks, prep sinks, pre-rinse sinks, can wash, floor drains, and dishwasher.
      (12)   Minimum concrete compressive strength of 3,500 psi.
      (13)   Watertight per vacuum test or water tightness test.
      (14)   Joints should be properly sealed to prevent infiltration or exfiltration.
      (15)   Grease interceptors must meet a minimum structural design of 150 pounds/square foot for non-traffic installations. For vehicular traffic conditions the grease interceptor shall be designed to withstand a H-20 wheel load.
      (16)   Grease interceptors shall meet the following standards: ASTM C-1227 for Septic Tanks, C-913 for Precast Concrete Water and Wastewater Structures, ACI-318 for Design and ASTM C-890 for establishing minimum structural design loading.
      (17)   Grease interceptors made of polyethylene or fiberglass tanks shall be able to withstand the appropriate loading (traffic or non-traffic) or perform under a vacuum test to stimulate loading and include 12,000 psi ultimate tensile strength, 19,000 psi flexural strength, and 800,000 psi flexural modulus of elasticity as per ASTM D790. Tanks shall be listed and labeled.
      (18)   A North Carolina design professional will specifically design cast in place or masonry tanks.
   (I)   Sizing.
      (1)   How to determine the size of an exterior, in-ground grease interceptor using the Manning Formula:
         (a)   The formula for calculating grease interceptor sizing is:
            Gallons of interceptor = [[(1) = GPM/fixture (derived from Manning Formula) x (2) = total # fixture ratings of grease-laden waste streams] + (3) direct flow from a dishwasher, can wash, mop sink (in GPM)]] x (4) = 24 minute retention time.
         (b)   Components of equation :
            1.   GPM/fixture—This is derived from the Manning Formula. It takes into account the slope; roughnesses of the pipe (plastic) used, and pipe diameter size. When applying the Manning Formula, we arrive at the drainage rates of various pipe diameter sizes:
               1.0 inch pipe diameter = 5.0 GPM/fixture
               1.5 inch pipe diameter = 15 GPM/fixture
               2.0 inch pipe diameter = 33 GPM/fixture
               2.5 inch pipe diameter = 59 GPM/fixture
               3.0 inch pipe diameter = 93 GPM/fixture
            2.   Fixture ratings of grease-laden waste streams: Fixtures that have more grease in their waste stream received higher values while less grease corresponds to a lower value. The table is shown below:
               Table of Common Commercial Kitchen Fixtures and their Corresponding Rating (each):
                  2, 3, or 4 compartment pot sink = 1.0
                  1 or 2 compartment meat prep sink = 0.75
                  Pre-rinse sink = 0.5
                  1 or 2 compartment vegetable prep sink = 0.25
            3.   Direct flow from dishwashers, can wash, mop sink and garbage disposal: use the following gpm values: Dishwasher rate of 10 gpm, can wash, mop sink and garbage disposal rate of 6 gpm.
            4.   Twenty-four-minute retention time: Engineers have determined that when applying several criteria to determine proper grease (animal and vegetable lipids) separation (using Stokes' Law, specific gravity of lipids, etc.), a 24-minute retention time is required.
Example 1: GPM x Grease Factor
(1) 3 Compartment Pot Sink, 1.5 waste drain
15 x 1.0 = 15.00 gpm
(1) 1 Compartment Pre-Rinse Sink, 1.5 waste drain
15 x 0.5 = 7.50 gmp
(1) 1 Compartment Prep Sink (Meat), 1.5 waste drain
15 x 0.75 = 11.25 gmp
(1) 1 Compartment Prep Sink (Vegetable), 1.5 waste drain
15 x 0.25 = 3.75 gpm
(1) Can Wash (Use 6 gpm)
   = 6.00 gpm
    43.50 gpm
   TOTAL gpm = 43.5 x 24 minutes retention time = 1,044 gallons
   MINIMUM 1,000 GALLON GREASE INTERCEPTOR REQUIRED
Example 2: GPM x Grease Factor
(1) 3 Compartment Pot Sink, 2.0 waste drain
33 x 1.0 = 33.00 gpm
(1) 1 Compartment Prep Sink (Meat), 1.5 waste drain
15 x 0.75 = 11.25 gpm
(1) 1 Compartment Prep Sink (Vegetable), 1.5 waste drain
15 x 0.25 = 3.75 gpm
(1) Pre-rinse Sink, 2.0 waste drain
33 x .05 = 16.50 gpm
(1) Dishwasher
   = 10.00 gpm
(1) Mop Sink, 3" waste drain
   = 6.00 gpm
 
    80.50 gpm
   TOTAL gpm = 80.5 x 24 minutes retention time = 1,932 gallons
   MINIMUM 2,000 GALLON GREASE INTERCEPTOR REQUIRED
 
      (2)   How to determine the size of a point-of-use grease interceptor:
 
Step 1
Determine the cubic contents of the fixture by multiplying length x width x depth.
Number of compartments times 24 inches long by 24 inches wide by 14 inches deep. Cubic contents: 3 x 24 x 24 x 14 = 24,192 cubic inches
Step 2
Determine the capacity in gallons 1 gallon = 231 cubic inches.
Contents in gallons: 24,192 (231 = 104.7 gallons)
Step 3
Determine actual drainage load. The fixture is usually filled to about 75% of capacity with wastewater. The items to be washed displace about 25% of the fixture content. Actual drainage load = 75% of fixture capacity.
Actual Load: .75 x 104.73 gallons = 78.55 gallons
Step 4
For design considerations, it is good practice to calculate the flow rate in GPM equal to or greater than 75% of the fixture capacity.
Calculated flow rate for design capacity in GPM on 75% of fixture capacity: 75% of fixture capacity = 78.55 gallons
Flow Rate = 78.55 GPM
Step 5
Select the grease separation device that matches the calculated design flow rate.
Note: Select next larger size when flow rate falls between two sizes.
79 GPM
 
   (J)   Service records. All food service establishments shall maintain a written record on site of grease interceptor maintenance record for three years. Documentation must include at a minimum the date and time of the service; the name of the grease contractor; and the location of the grease treatment/disposal facility. All grease interceptor maintenance records shall be approved by the Director. A copy of each maintenance record shall be mailed to the county, at the address indicated below, no later than 15 days after the end of the month during which the maintenance occurred. Any person who fails to comply with this section is subject to enforcement actions as outlined in division (R). Failure to submit monthly maintenance records for two consecutive months may result in an inspection.
   (K)   Existing facilities with grease interceptors.
      (1)   All existing food service establishments shall maintain grease interceptors for continuous, satisfactory and effective operation.
      (2)   Maintenance shall include the complete removal of all contents, including floatable materials, wastewater, sludge, and solids. Separation, decanting or back flushing of the grease interceptor or its wastes is prohibited.
      (3)   The food service establishment should have a licensed North Carolina Septage Management Firm service all interceptors at intervals not to exceed 30 days.
      (4)   All food service establishments shall inspect the grease interceptor at the time of service or prior to opening business if the interceptor is serviced after hours and shall report to the Utilities Director any conditions that do not comply with the sewer use resolution and/or grease control policy.
      (5)   Grease maintenance service records shall be submitted as stated in division (J).
      (6)   Any additional fixtures that are added to the food service establishment and discharge a grease-laden waste stream as identified in division (I) shall be plumbed into the interceptor and/or a new interceptor may be required.
   (L)   Food service establishment in new facilities.
      (1)   Food service establishments, locating in newly constructed facilities, shall install a grease interceptor adequately sized and approved by the county. Facilities are not allowed to share grease interceptor devices.
      (2)   All new grease interceptors shall be designed and constructed in accordance to divisions (H) and (I).
      (3)   No new food service establishment will be allowed to initiate operations until grease interceptors are approved and inspected by the county.
      (4)   Following installation of a grease interceptor, all food service establishments shall comply with maintenance requirements as set forth in division (K).
      (5)   Food service establishments with a bona fide hardship of a physical property restriction shall install a point-of-use grease interceptor. Construction and maintenance shall follow division (M).
   (M)   New food service establishments in existing facilities.
      (1)   New food service establishments locating in existing buildings are required to comply with the grease interceptor standards applicable to new facilities, as set forth herein.
      (2)   For cases in which exterior type grease interceptors are infeasible to install due to physical property restrictions, a "point-of-use" grease trap shall be installed. The "point of use” grease trap shall comply with sizing criteria. More than one fixture can be plumbed into a single grease interceptor, however, the grease interceptor size shall be equal to the total fixture capacity for all fixtures which the interceptor serves. Flow control fittings must be provided to the inlet side of all point-of-use if required by the manufacturer. Maintenance procedures shall follow in a later section. Dishwashers shall not be plumbed into a point-of-use grease interceptor.
      (3)   The county must approve control devices and grease interceptor design prior to installation.
   (N)   New buildings (strip centers) with the potential for food service establishments. All new buildings or strip centers containing sections designated for commercial enterprise of the strip center are encouraged to provide a stub-out for a separate waste line for future grease interceptor installation. The owner of a new strip center shall consider suitable physical property space and sewer gradient that will be conducive for the installation of an exterior, in-ground grease interceptor(s) for any flex space contained within the strip center. Physical property restrictions and sewer gradient shall not be a defense for failure to install an exterior, in-ground grease interceptor.
   (O)   Substandard grease interceptors.
      (1)   Any food service establishment without a grease interceptor will be given a compliance deadline not to exceed six months from date of notification to have approved and installed grease interceptors.
      (2)   In the event an existing food service establishment's grease interceptors are either under-designed or substandard in accordance with this policy, the owner(s) will be notified in writing of the deficiencies and required improvements, and given a compliance deadline not to exceed six months to conform with the requirements of this standard. An exterior in-ground interceptor will be required and installation and maintenance shall follow in this policy.
      (3)   For cases in which exterior type grease interceptors are infeasible to install due to physical property restrictions, a “point-of-use” grease trap shall comply with sizing criteria specified in this chapter. More than one fixture can be plumbed into a single grease interceptor however, the grease interceptor size shall be equal to the total fixture capacity for all fixtures which the interceptor serves. Flow control fittings must be provided to the inlet side of all point-of-use if required by the manufacturer. Maintenance procedures shall follow division (K). Dishwashers shall not be plumbed into a point-of-use grease interceptor.
      (4)   The Director must approve control devices and grease interceptor design prior to installation.
   (P)   Variance. 
      (1)   A variance to exceed the requirement set forth in division (K) which sets the scheduled maintenance requirements for all grease interceptors at intervals not to exceed 30 days (for interceptors equal to or greater than 500 gallons), may be requested of the county upon submission of sufficient information and documentation. Such documentation shall provide a written explanation for the need to vary from the maintenance schedule requirements of this chapter. After submission of a request to the county, the county will review all information submitted and will notify the food service establishment in writing of its acceptance or denial of the variance request. All food service establishments requesting a variance shall agree to submit to a variance study. The county has the right to discontinue the variance study at any time the grease interceptor discharge adversely affects the sanitary sewer collection system or treatment works.
      (2)   Fees associated with the request of a variance will include a variance fee of $300, which includes estimated costs associated with the variance study. All fees are nonrefundable and shall be paid in advance.
      (3)   A variance to exceed the 30-day interval requirement for scheduled maintenance set forth in division (K) may be granted if the accumulated grease cap and sludge pocket measurements remain below 25% of the total depth from the grease interceptor's interior floor to the static or working water level, at any point between the influent and effluent pipes/baffles of the grease interceptor. No variance will be granted to exceed a 180-day interval, with the exception of schools and seasonal event facilities and any other FSE as determined by the Director, who may exceed a 180-day interval upon submitting a request in writing to the Director and receiving written permission from the Director.
      (4)   (a)   Any food service establishment who is found to violate the 25% rule as set forth in divisions herein below, may be required to pump more frequently than monthly.
         (b)   Variance study procedure. Once a variance has been granted, a variance study shall be conducted in accordance with the following procedure:
            1.   Prior to a variance study, the grease interceptor shall be completely pumped and sufficiently cleaned by a servicing company at the user's expense. A variance study cannot be conducted unless the grease interceptor is properly serviced, as determined by the county.
            2.   The food service establishment shall contact the county two working days prior to the scheduled interceptor cleaning.
            3.   Once the grease interceptor is cleaned properly and refilled with water from the food service establishment, the county will conduct a visual inspection of the grease interceptor and verify that all components of the trap are in place and in proper working order. If a grease interceptor fails the visual inspection, the food service establishment shall correct all inadequacies at the owner's expense. The food service establishment shall notify the county in writing of all corrected measures upon completion. Such notification shall be mailed to the address set forth in § 53.001(A)(2).
            4.   Two weeks after initial pumping, the county will measure the grease cap and sludge pocket to obtain data to determine grease interceptor performance.
            5.   Four weeks after the initial pumping, the county will re-measure the grease cap and sludge pocket to further evaluate grease interceptor performance.
            6.   This process will continue on a biweekly frequency until the accumulated grease cap and sludge pocket reach 25% of the total depth of the grease interceptor. Variance studies shall not exceed a period of 90 days.
            7.   The county will review all data obtained, and submit in writing the results of the variance. The result will only be furnished to the food service establishment requesting the variance.
            8.   The county will not be responsible for any grease discharge, odor, or blockages associated during or after the variance study. At no time during the variance study shall the grease interceptor be pumped, except by direct approval of the county.
      (5)   Variance revocation. A variance to exceed the 30-day interval requirement for scheduled maintenance may be revoked by the county, at its discretion, if at any time after a variance is granted the following occurs:
         (a)   Grease interceptor discharge adversely affects the sewer collection system or treatment works.
         (b)   Grease and solids accumulation is greater than 25% of the total depth from grease interceptor's interior floor to the static or working water level, at any point within the grease interceptor.
         (c)   A food service establishment significantly increases food service production, seating capacity, or menu change.
         (d)   A food service establishment causes or contributes to a sanitary sewer blockage or overflow.
   (Q)   Prohibitions and violations. No user shall contribute or cause to be contributed into the sanitary sewer system the following:
      (1)   Hot water running continuously through grease interceptor.
      (2)   Discharge of concentrated alkaline or acidic solutions into a grease interceptor.
      (3)   Discharge of concentrated detergents into grease traps.
      (4)   Discharge of oils and grease into the sanitary sewer system.
      (5)   It shall be a violation of this policy for any person or user to:
         (a)   Modify a grease interceptor structure without consent from the county.
         (b)   Provide falsified maintenance records.
         (c)   Not comply with this policy.
   (R)   Enforcement. 
      (1)   Any food service establishment that is identified, in whole or in part, as the source of a sanitary sewer blockage and/or overflow, will be assessed a fine of not less than $500 and not more than $25,000, plus remediation costs for cleanup, in addition to any fines dispensed from the State of North Carolina.
      (2)   Food service establishments committing one of the offenses listed herein will be assessed the corresponding amounts on a calendar year basis. These fines will be billed no less than monthly and are payable upon receipt. The fines provided for in this section are not exclusive and do not prohibit the Director from using any other remedy provided by law.
         (a)   Minor violation.
            1st offense:
            Failure to submit records: $50
            Inspection hindrance (equipment related: $50
            Failure to maintain on site record: $50
            Failure to pump grease and submit record: $150
 
            2nd offense:
            Failure to submit records: $100
            Inspection hindrance (equipment related): $100
            Failure to maintain on site records: $100
            Failure to pump grease and submit records: $300
 
            3rd offense:
            Failure to submit records: $150
            Inspection hindrance (equipment related): $150
            Failure to maintain on site record: $150
            Failure to pump grease and submit records: $450
 
            4th offense and up:
            Failure to submit records: $300
            Inspection hindrance (equipment related): $300
            Failure to maintain on site records: $300
            Failure to pump grease and submit records: $1,000
         (b)   Intermediate violation. Failure to maintain necessary equipment (T's, grease trap not watertight, baffles, etc.):
            1st offense: $150
            2nd offense: $300
            3rd offense: $500
            4th offense and up: $1,000
         (c)   Major violation.
            Source of sewer blockage (minimum): $500
            Source of sanitary sewer overflow (minimum): $1,000
            Falsification of maintenance records: $1,000
   (S)   Appeal of grease policy.
      (1)   Any food service establishment (FSE) may appeal a fine that has been assessed for failure to comply with the grease control policy. The FSE must submit a written request, identifying the specific issues to be contested, to the Grease Compliance Officer within 30 days following receipt of the water bill, assessment of fine, or notice of violation. Unless such written request is made within the time frame specified, the fine subject to appeal shall be final and binding. The Grease Compliance Officer and the Industrial Waste Control Supervisor shall evaluate the information and shall make a written decision within 15 days of receipt of the appeal request.
      (2)   The decision made above may be appealed by any party, to the Director of Utilities upon filing a written demand within ten days of receipt of notice of the previous decision. A meeting will be held to evaluate information. Failure to make written demand within the specified time herein shall bar further appeal. The Director shall make a decision on the appeal within 90 days of the date the appeal was filed. Further appeal shall follow § 53.106.
(Ord. passed 12-4-2017)