§ 51.111 TYPE; SPECIFICATIONS.
   (A)   The make and model of fire hydrants installed shall be approved by the Town Council.
(Prior Code, § 3.1C.31)
   (B)   Every fire hydrant installed within the town or surrounding zoning area shall have:
      (1)   Minimum of two 2-1/2 inch connections;
      (2)   Minimum of one 4-1/2 inch connections;
      (3)   All threads to be NST thread;
      (4)   Side six inch;
      (5)   Five and one-quarter inch valve opening;
      (6)   Five and one-half inch bury depth;
      (7)   Three hundred sixty degree upper section rotation;
      (8)   Open left (CCW);
      (9)   Seven-inch inside barrel diameter minimum; and
      (10)   Auxiliary shut-off.
(Prior Code, §§ 3.1C.31, 3.1C.32) (Ord. 95-009, passed - -1995)