§ 155.25 STANDARDS FOR ACCESSORY STRUCTURES IN ALL "A" ZONES.
   For all accessory structures in special flood hazard areas designated "A" the following provisions shall apply:
   (A)   Structure must be non-habitable;
   (B)   Must be anchored to resist floatation forces;
   (C)   Will require flood openings/vents no more than one foot above grade; total openings are to be one square inch per one square foot of floor area; at least two openings required on opposite walls;
   (D)   Built of flood resistant materials below a level two feet above the base flood elevation;
   (E)   Must elevate utilities above the base flood elevation;
   (F)   Can only be used for storage or parking; and
   (G)   Cannot be modified for a different use after permitting.
(Ord. 2011-3, passed 4-11-11) Penalty, see § 155.99