For all accessory structures in special flood hazard areas designated "A" the following provisions shall apply:
(A) Structure must be non-habitable;
(B) Must be anchored to resist floatation forces;
(C) Will require flood openings/vents no more than one foot above grade; total openings are to be one square inch per one square foot of floor area; at least two openings required on opposite walls;
(D) Built of flood resistant materials below a level two feet above the base flood elevation;
(E) Must elevate utilities above the base flood elevation;
(F) Can only be used for storage or parking; and
(G) Cannot be modified for a different use after permitting.
(Ord. 2011-3, passed 4-11-11) Penalty, see § 155.99