(a) Fire hydrants with two and one half (2-1/2) inch outlets and one (1) large pumping connection shall be provided by the subdivider in all subdivisions with public water supplies. The hydrants should be located between property lines and curbs with all outlets facing or parallel to the street. Hydrants shall be placed at the corners of all blocks and at mid-block for blocks exceeding eight hundred (800) feet in length. Hydrants shall also be required at the entrance and end of all cul-de-sacs exceeding four hundred (400) feet in length.
(b) The type of hydrant and control valves and the location of the hydrant shall be approved by the Fire Chief. The minimum size of any water line serving any hydrant shall not be less than six (6) inches in diameter and should be circulating water lines. The size and location of water lines should be approved by the Village Engineer, the Fire Chief, and the Ohio Inspection Bureau for commercial and industrial subdivisions.
(Ord. 1991-4. Passed 5-13-91.)