§ 103.02 GEOTHERMAL SYSTEM.
   (A)   A closed loop geothermal system must be located so as to be easily accessed and must not be built over or placed under impervious materials.
   (B)   Piping for a closed loop geothermal system must be bedded so as to prevent freezing or undue compaction pressure.
   (C)   Piping used for a closed loop geothermal system must be constructed of polyethylene pipe, or its equivalent, having a pressure resistance of 160 psi and a SDR of seven.
   (D)   Any coolant or other chemical additive used in any closed loop geothermal system must be non-toxic (i.e., consumable by humans and easily degradable) such that it would not be injurious to the public health or health of the environment in the event of a spill, leak or other release.
   (E)   No vertical geothermal systems are permitted within the city.
   (F)   No open loop geothermal systems are permitted within the city.
(Ord. 2008-25, passed 12-9-2008) Penalty, see § 103.99