11-2-2-3: ELECTRICAL DISTRIBUTION SYSTEM:
   (A)   Definition: "Mobile home development electrical wiring system" shall mean all of the electrical wiring, fixtures, equipment and appurtenances related to electrical installations within a mobile home development, up to the mobile home service entrance conductor, or if none, the mobile home service equipment.
   (B)   Compliance With Adopted Code: Except as otherwise permitted or required by this standard, all electrical installations in mobile home developments shall be designed and constructed in accordance with the applicable electrical code adopted by the enforcing agency.
   (C)   Distribution System: The mobile home development secondary electrical distribution system to mobile home lots shall be single phase, 120/240 volts.
   (D)   Calculated Load:
      1.   Mobile home development electrical wiring systems shall be calculated on the basis of not less than sixteen thousand (16,000) watts (at 120/240 volts) per each mobile home service. The demand factors which are set forth in the following table are the minimum allowable demand factors which may be used in calculating load on feeders and service.
Number Of Mobile Home Lots
Demand Factor (Percent)
      1
      100
      2
      55
      5
      33
      10
      27
      20
      25
      50
      23
      100   and over
      22
 
      2.   For the purpose of this subsection, where the development service exceeds two hundred forty (240) volts, transformers and secondary distribution panel boards shall be treated as services.
      3.   Mobile home lot feeder circuit conductors shall have adequate capacity for the loads supplied, and shall be rated at not less than one hundred (100) amperes at 120/240 volts.
   (E)   Mobile Home Service Equipment:
      1.   Mobile home service equipment shall be rated at not less than one hundred (100) amperes. Provision may be made for connecting a mobile home power supply assembly by a permanent wiring method which may have fifty (50) ampere receptacles conforming to applicable electrical codes.
      2.   Mobile home service equipment may also be provided with a means for connecting a mobile home accessory building or structure or additional electrical equipment located outside a mobile home by a permanent wiring method.
      3.   Additional receptacles may be provided for connection of electrical equipment located outside the mobile home.
      4.   The point of the electrical connection for the mobile home will be within the area of the mobile home stand and approximately forty feet (40') from the front of such stand. (Ord. 45, 3-19-1973)