Loading...
(A) Backflow prevention and cross-connection standards. Every source of contamination or possible contamination from any contaminant which originates from or is located at a residential, commercial or industrial establishment, which is connected to any public water supply shall be equipped with the protection required under the provisions of this section.
(B) Definitions. For the purpose of this section, the following definitions apply unless the context clearly indicates or requires a different meaning. If a word or term used in this section is not contained in the following list, its definition, or other technical terms used, shall have the meanings or definitions listed in the most recent adopted edition of the City of Cleburne Plumbing Code and/or (M14) AWWA Manual of Water Supply Practices - "Recommended Practice For Backflow Prevention and Cross-Connection."
AIR GAP. A physical separation between the free flowing discharge end of a potable water supply piping and/or appurtenance and an open or non-pressure receiving vessel, plumbing fixture or other device. An "approved air-gap separation" shall be at least twice the diameter of the supply pipe measured vertically above the overflow rim of the vessel, plumbing fixture or other device in no case less than one inch.
ATMOSPHERIC VACUUM BREAKER BACKFLOW PREVENTION DEVICE or ATMOSPHERIC VACUUM BREAKER or "AVB." A device used to prevent backsiphonage in non-health hazard conditions. This device cannot be tested and cannot prevent backpressure backflow.
AUXILIARY SUPPLY. Any water source or system other than the public water system, that may be available in the building or on the property, including ground water or surface waters used for industrial, irrigation or any other purpose.
BACKFLOW. The flow in the direction opposite to the normal flow or the introduction of any foreign liquids, gases, or substances into the water system of the city's water.
BACKFLOW PREVENTION ASSEMBLY or ASSEMBLY. An assembly to counteract back pressure or prevent backsiphonage.
BACKPRESSURE. Any elevation of pressure in the downstream piping system (by any means) above the supply pressure at the point of consideration which would cause, or tend to cause, a reversal of the normal direction of flow and the introduction of fluids, mixtures or substances from any source other than the intended source.
BACKSIPHONAGE. The flow of water or other liquids, mixture or substances into the distribution pipes of a potable water supply system from any source other than its intended source caused by a sudden reduction of pressure in the potable water supply system.
BORESIGHT or BORESIGHT TO DAYLIGHT. Providing adequate drainage for backflow prevention assemblies installed in vaults through the use of an unobstructed drain pipe.
COMMERCIAL OR INDUSTRIAL ESTABLISHMENT. Property or location which is used primarily for manufacture, production, storage, wholesaling or retailing of products or services which are or may be placed in the flow of commerce or any property or location which is used primarily for the provision of any service.
COMMISSION. The Texas Commission on Environmental Quality (TCEQ).
CONTAMINANTS. Any foreign material, solid or liquid, not common to the potable water supply which makes the water unfit or undesirable for human or animal consumption.
CONTAMINATION. The admission of contaminants into the potable water supply system.
CROSS-CONNECTION. Any connection, physical or otherwise, between a potable water supply system and any plumbing fixture or any tank, receptacle, equipment or device, through which it is possible for any nonpotable, used, unclean, polluted and contaminated water, or other substances, to enter into any part of such potable water system under any condition or set of conditions.
CROSS-CONNECTION CONTROL DEVICE. Any nationally approved or recognized device placed upon any connection, physical or otherwise, between a potable water supply system and any plumbing fixture or any tank, receptacle, equipment or device, which is designed to prevent nonpotable, used, unclean, polluted and contaminated water, or other substances, from entering into any part of such potable water system under any condition or set of conditions.
CUSTOMER SERVICE INSPECTION. An inspection designed to inspect and detect any actual or potential cross-connection hazards and/or exceed of the lead action level in solder or flux, pipe or pipe fittings.
DEGREE OF HAZARD. The low or high hazard classification that shall be attached to all actual or potential cross-connections.
(1) Health hazard. An actual or potential threat of contamination of a physical or toxic nature to the public potable water system or the consumer's potable water system that would be a danger to health.
(2) High hazard. The classification assigned to an actual or potential cross-connection that potentially could allow a substance that may cause illness or death to backflow into the potable water supply.
(3) Low hazard. The classification assigned to an actual or potential cross-connections that potentially could allow a substance that may be objectionable but not hazardous to one's health to backflow into the potable water supply.
(4) Pollution hazard. An actual or potential threat to the physical properties of the water system or the potability of the public or the consumer's potable water system but which would not constitute a health or system hazard, as defined. Maximum degree of intensity of pollution which the potable water system could be degraded under this definition would cause a nuisance or be aesthetically objectionable or could cause damage to the system or its appurtenances.
(5) System hazard. An actual or potential threat of severe danger to the physical properties of the public or consumer's potable water supply or of a pollution or contamination that would have a detrimental effect on the quality of the potable water in the system.
DIRECTOR. The Building Official or his designee who is vested with the authority and responsibility for the implementation of an effective cross-connection control program and for the enforcement of the provisions of this section.
DOUBLE CHECK DETECTOR BACKFLOW PREVENTION ASSEMBLY or DOUBLE CHECK DETECTOR ASSEMBLY or DCDA. An assembly composed of a line-size approved double check assembly with a bypass containing a specific water meter and an approved double check valve assembly. The meter shall register accurately for very low rates of flow.
DOUBLE CHECK VALVE BACKFLOW PREVENTION ASSEMBLY or DOUBLE CHECK ASSEMBLY or DOUBLE CHECK or DC. An assembly which consists of two independently acting, approved check valves, including tightly closing resilient seated shutoff valves attached at each end of the assembly and fitted with properly located resilient seated test cocks.
FIRELINE TESTER. A tester who is employed by a state approved fireline contractor and is certified by TNRCC to test backflow prevention assemblies on firelines only. Tester must also be registered with the City of Cleburne Inspection Department.
GENERAL TESTER. A tester who is certified by TNRCC to test backflow prevention assemblies on any domestic, commercial, industrial or irrigation service except firelines. Tester must also be registered with the City of Cleburne Inspection Department.
MOBILE UNIT. Any operation which may have the potential to introduce contaminants into a potable water system from a mobile source. These include, but are not limited to, carpet-cleaning vehicles, water-hauling vehicles, street-cleaning vehicles, liquid-waste vehicles, power-wash operations and pest-control vehicles.
NON-RESIDENTIAL USE. Water used by any person other than a residential customer of the water supply and include all uses not specifically included in "residential uses".
PERSON. Any individual, partnership, associations, corporations, firms, clubs, trustees, receivers, and bodies political subdivision and corporate.
POINT-OF-USE ISOLATION. The appropriate backflow prevention within the consumer's water system at the point at which the actual or potential cross-connection exists.
POTABLE WATER SUPPLY. Any water supply intended or used for human consumption or other domestic use.
PREMISES. Any piece of property to which water is provided, including all improvements, mobile structures, and structures located on it.
PREMISES ISOLATION. The appropriate backflow prevention at the service connection between the public water system and the water user.
PRESSURE VACUUM BREAKER BACKFLOW PREVENTION ASSEMBLY or PRESSURE VACUUM BREAKER or "PVB". An assembly which provides protection against backsiphonage, but does not provide adequate protection against backpressure backflow. The assembly is a combination of a single check valve with an AVB and can be used with downstream resilient seated shutoff valves. In addition, the assembly has suction and discharge gate valves and resilient seated test cocks which allow the full testing of the assembly.
PUBLIC WATER SYSTEM or SYSTEM. Any public or privately owned water system which supplies water for public domestic use. The system will include all services, reservoirs, facilities, and any equipment used in the process of producing, treating, storing, or conveying water for public consumption.
REDUCED PRESSURE PRINCIPLE BACKFLOW PREVENTION ASSEMBLY or REDUCED PRESSURE PRINCIPLE ASSEMBLY or RP ASSEMBLY or RP. An assembly containing two independently acting approved check valves together with a hydraulically operated, mechanically independent pressure differential relief valve located between the check valves and at the same time below the first check valve. The assembly shall include properly located resilient seated test cocks and a tightly closing resilient seated shutoff valve at the end of the assembly.
REDUCED PRESSURE PRINCIPLE DETECTOR BACKFLOW PREVENTION ASSEMBLY or REDUCED PRESSURE DETECTOR or RPDA. An assembly composed of a line-size approved reduced pressure principle assembly with a bypass containing a specific water meter and an approved reduced pressure principle backflow prevention assembly. The meter shall register accurately for very low rates of flow.
REGULATORY AUTHORITY. Any Municipal Officer or department of the city, appointed by the City Manager to administer this section.
REPRESENTATIVE OF THE WATER SYSTEM. A person designated by the city to perform cross-connection control duties that shall include, but are not limited to, cross-connection inspection and water use surveys.
RESIDENTIAL USE. Water used by any residential customer of the water supply and include single family dwellings, duplexes, multiplex, housing and apartments where the individual units are each on a separate meter, or, in cases where two or more units are served by one meter, the units are full-time dwellings.
SERVICE CONNECTION. The point of delivery at which the water purveyor looses control of the water.
SPILL-RESISTANT PRESSURE VACUUM BREAKER or SVB. An assembly containing an independently operating, internally loaded check valve and independently operating, loaded air inlet valve located on the discharge side of the check valve. This assembly is to be equipped with a properly located resilient seated test cock and tightly closing resilient seated shutoff valves attached at each end of the assembly.
TCEQ. Texas Commission on Environmental Quality.
THERMAL EXPANSION. The space needed for heated water to expand.
USED WATER. Water supplied by a public water system to a water user's system after it has passed through the service connection.
(C) Right of way encroachment. No person shall install or maintain a backflow assembly upon or within any city right-of-way except as provided in this section.
(1) A backflow prevention assembly required by the city may be installed upon or within any city right-of-way only if the owner proves to the city that there is no other feasible location for installing the assembly, and installing it in the right-of-way will not interfere with traffic or utilities. The city retains the right to approve the location, height, depth, enclosure, and other requisites of the assembly prior to its installation.
(2) All permits and inspections required by the City Code to perform work in the right-of-way shall be obtained.
(3) The assembly shall be installed below or flush with the surrounding grade except when it is not practicable to install it in this manner. Any assembly or portion of an assembly which extends aboveground shall be located no closer than 18 inches to the face of the curb.
(4) The city shall not be liable for any damage done to or caused by an assembly installed in a right-of-way.
(5) A property owner shall, at the request of the city and at the owner's expense, relocate a backflow prevention assembly which encroaches upon any city right-of-way when such relocation is necessary for street or utility construction or repairs for purposes of public safety.
(6) A person commits an offense if he/she fails to relocate a backflow prevention assembly located in or upon any city right-of-way after receiving a written order from the regulatory authority to do so.
(D) Multiple connections. Any premises requiring multiple service connections for adequacy of supply and/or fire protection will be required to install a backflow assembly on each of the additional service lines to the premises. The type of assembly will be determined by the degree of hazard that could occur in the event of an interconnect between any of the buildings on the premises.
(E) Protection required; installation.
(1) The backflow prevention assembly protection which is required under this section shall be any of the duly nationally recognized and authorized backflow prevention assemblies listed in a state approved Plumbing Code, or as determined by the regulatory authority. Each backflow prevention assembly must have been approved by the regulatory authority prior to installation. Failure to obtain such approval prior to installation of the backflow prevention assembly may result in the backflow prevention assembly failing to meet approval by the regulatory authority. The regulatory authority shall approve the type and location of backflow assembly to be installed within the area served by the city. The assembly will be required in each of the following circumstances, but the representative is in no way limited to the following circumstances:
(a) The nature and extent of any activity of the premises, or the materials used in connection with any activity of the premises, or material stored on the premises, could contaminate or pollute the potable water supply.
(b) Premises having any one or more cross-connections identified or are present.
(c) Premises having any one or more cross-connections and the cross-connection(s) is protected by an atmospheric vacuum breaker device (AVB).
(d) Internal cross-connections are present that are not correctable.
(e) Intricate plumbing arrangements that are present which make it impractical to ascertain whether cross-connections exist.
(f) There is a repeated history of cross-connections being established or re-established.
(g) There is unduly restricted entry so that inspections for cross-connections cannot be made with sufficient frequency to assure that cross-connections do not exist.
(h) Materials are being used such that, if backflow should occur, a health hazard could result.
(i) Installation of an approved backflow prevention assembly is deemed to be necessary to accomplish the purpose of these regulations in the judgment of the city.
(j) An appropriate cross-connection survey report form has not been filed with the Building Inspection Department of the city upon request of the city.
(k) A fire sprinkler system that is connected to the city's water system.
(l) All new construction if deemed necessary in the customer service inspection. The type of assembly required will be commensurate with the degree of hazards determined by the regulatory authority.
(m) When a building is constructed on commercial premises, and the end use of such building is not determined or could change, a double check backflow prevention assembly may be installed at the meter connection that supplies water for public domestic use. If a different use, another device may also be required.
(n) Any used water return system.
(o) In the event a point-of-use assembly has not had the testing or repair done as required by this section, a premises isolation assembly will be required.
(p) If it is determined that additions or alterations have been made to the plumbing system without obtaining proper permits, premises isolation may be required.
(q) All multi-story buildings or any building with a booster pump or elevated storage tank.
(r) Retro-fitting will be required on all high hazard connections and wherever else the city deems necessary to retrofit.
(2) All backflow prevention assemblies installed after the effective date of this section shall be installed in a manner designed to facilitate ease of inspection by the regulatory authority of the city or his chosen representative. Any currently installed backflow prevention assemblies which are located in inaccessible locations, or where the tester is subject to physical danger, shall be relocated to approved locations following current plumbing code or AWWA M14 Manual guideline standards.
(3) Anytime a backflow device is installed in a primary water supply line of potable water, an expansion tank will be required on all water heaters and/or boilers.
(F) Testing of assemblies.
(1) The regulatory authority shall inspect and require the installer/property owner to test all backflow prevention assemblies in each of the following circumstances:
(a) Immediately after installations;
(b) Whenever the assembly is moved;
(c) A minimum of once a year for all backflow devices on hazardous locations.
(d) Premises that have been vacated and unoccupied for one year, prior to re-occupancy;
(e) Immediately after repairs.
(f) All grandfathered, non-conforming devices will be removed and replaced with approved equipment under the following:
1. Major repairs;
2. Modifications to the water system;
3. Report of failure of current backflow device.
(2) All assembly testing shall be performed by a TNRCC certified backflow prevention assembly tester, approved by the regulatory authority.
(3) Duly authorized employees of the city bearing proper credentials and identification are entitled to enter any public or private property at any reasonable time for the purpose of enforcing this section. Persons and occupants of premises which are provided water service by the city, either directly or indirectly, shall allow the city or their representatives ready access at all reasonable times to all parts of the premises for the purposes of inspection, testing, records, examination, or in the performance of any of their duties. Where persons or occupants of premises have security measures in force which would require proper identification and clearance before entry into their premises, the persons and occupants of the premises shall make necessary arrangements with their security guards so that upon presentation of suitable identification, personnel from the city will be permitted to enter, without delay, for the purposes of performing their specific responsibilities.
(4) The city is not liable for damage to a backflow prevention assembly which may occur during testing.
(5) The regulatory authority may cause a water use survey to be conducted at any establishment located in the city which is served by a public water supply or which provides water to the public. Upon determination by the regulatory authority that the establishment falls under the provisions of this section and requires a backflow prevention assembly, the regulatory authority shall issue a notice to abate the condition or order the establishment to install the proper backflow prevention assembly.
(6) It is the responsibility of any person who owns or controls property to have all assemblies tested in accordance with this section. Assemblies may be required to be tested more frequently if the regulatory authority deems necessary.
(7) All results from assembly testing by a certified backflow prevention assembly tester shall be placed on a form that is purchased by the tester from the city for an established fee.
(G) Thermal expansion. It is the responsibility of any person who owns or controls property to eliminate the possibility of thermal expansion, if a closed system has been created by the installation of a backflow assembly.
(H) Pressure loss. Any reduction in water pressure caused by the installation of a backflow assembly is not the responsibility of the city.
(I) Residential service connections. Any person who owns or controls any residential property which has been determined to have an actual or potential cross-connection will be required to eliminate the actual or potential cross-connection or have an approved backflow assembly installed in accordance with this section.
(J) Rental properties. Any person who owns or controls property is responsible for the installation, testing and repair of all backflow assemblies on their property.
(K) Customer service inspection.
(1) Pursuant to TNRCC Water System Regulations, a customer service inspection for cross-connection control shall be completed by the regulatory authority prior to providing continuous water service in each of the following circumstances:
(a) Water service to a newly constructed facility or previously nonexisting premises;
(b) After any material improvement to building(s) or premises;
(c) Any correction or addition to the plumbing of any facility or premises;
(d) The regulatory authority suspects a health hazard or potential cross-connection exists.
(2) Permanent water service shall not be supplied to a new construction facility(s) until after the customer service inspection is completed by the Regulatory Authority or representative.
(3) Temporary water service which poses a potential cross-connection threat to the potable water supply shall be protected by an approved backflow prevention assembly.
(L) Installation guidelines and requirements for backflow prevention assemblies.
(1) General. To insure proper operation and accessibility of all backflow prevention assemblies, the following requirements shall apply to the installation of these assemblies.
(a) Backflow prevention assemblies shall be installed in accordance with the current TNRCC Rule and these regulations. The assembly installer must obtain the required plumbing permits and have the installation inspected by a representative of the regulatory authority and tested by a General Tester or Fire Tester.
(b) At those facilities where the regulatory authority requires a backflow prevention assembly be installed at the point of delivery of the water supply. Such installation of the assembly must be before any branch in the line and on private property located just inside the boundary between the city right of way and the landowner's property. The regulatory authority may specify other areas for installation of the assembly. Assemblies that must be installed or are located on city right of way are the responsibilities of the business or entity that the water line is serving.
(c) The assembly must be protected from freezing and other severe weather conditions.
(d) All backflow prevention assemblies shall be of a type and model approved by the regulatory authority.
(e) All vertical installations of backflow assemblies must have prior approval by the regulatory authority.
(f) Assemblies that are larger then 4 inches and installed more than 5 feet above floor level must have a suitable platform for use by testing or maintenance personnel.
(g) Bypass lines are prohibited. Pipe fittings which could be used for connecting a bypass line must not be installed.
(h) Premises where an uninterrupted water supply is critical should be provided with two assemblies installed in parallel. They should be sized in such a manner that either assembly will provide the maximum flow required.
(i) Lines should be thoroughly flushed prior to installation. A strainer with blowout tapping may be required ahead of the assembly.
(j) All facilities that require continuous, uninterrupted water service and are required to have a backflow assembly must make provisions for the parallel installation of assemblies of the same type so that testing, repair and maintenance can be performed.
(k) The property owner assumes all responsibility for any damages resulting from installation, operation, and/or maintenance of a backflow assembly. The owner shall be responsible for keeping all backflow prevention assembly vaults reasonably free of silt and debris.
(l) Upon completion of installation, the regulatory authority shall be notified and all assemblies must be inspected and tested. All assemblies must be registered with the regulatory authority and shall provide the date of installation, manufacturer, model, type, size, serial number or the backflow assembly, and initial test report by a certified tester.
(2) Reduced pressure principle backflow prevention assemblies (RPs). May be utilized at premises where a substance is handled that would be hazardous to health if introduced into the potable water system. The RP is normally used in locations where an air gap is impractical. The RP is effective against both backsiphonage and backpressure.
(a) RPs must be sized to provide an adequate supply of water and pressure for the premises being served. Flow characteristics are not standard. Consult manufacturer's specifications for specific performance data.
(b) The assembly must be readily accessible for testing and maintenance and must be located in an area where water damage to building or furnishing would not occur from relief valve discharge. The property owner assumes all responsibility for any damage caused by water discharge from an RP assembly. An approved air gap shall be located at the relief valve orifice of RP assemblies.
(c) No part of a reduced pressure principle backflow prevention assembly shall be submerged in water or installed in a location subject to flooding. RPs are typically installed above grade in well drained areas, but may be installed below grade (ground level) if a boresight drain to daylight is provided. The drain shall be of adequate capacity to carry the full rated flow of the assembly and shall be screened on both ends.
(d) Enclosures shall be designed for ready access and sized to allow for the minimum clearances established below. Removable protective enclosures are typically installed on the smaller assemblies. Daylight drain ports must be provided to accommodate full pressure discharge from the assembly.
(e) Assemblies 2 inches and smaller shall have at least 6 inch clearance on both sides and on top of the assembly, and 12 inches below and behind the assembly. All assemblies larger than 2 inches shall have a minimum of 12 inches on the back side, 24 inches on the test cock side, and the relief valve opening shall be at least 12 inches plus nominal size of assembly above the floor or highest possible water level. Headroom of 6 feet 0 inches is required in vaults without a fully removable top. A minimum access opening of 36 inches is required on all vault lids.
(f) All RP assemblies must be tested in accordance with this section. Tests are the responsibility of the assembly owner. The owner must notify the regulatory authority upon installation of any backflow prevention assembly.
(g) Variances from these specifications will be evaluated on a case-by-case basis. Any deviations must have prior written approval of the regulatory authority.
(2) Reduced pressure principle detector backflow prevention assemblies (RPDA). May be utilized in all installations requiring a reduced pressure principle backflow prevention assembly and detector metering.
(a) RPDAs shall comply with the installation requirements applicable for reduced pressure principle backflow assemblies (RP).
(b) The line-size RP assembly and the bypass RP assembly must each be tested. A separate test report for each assembly must be completed by the certified tester.
(3) Double check valve backflow prevention assemblies (DC). May be utilized at premises where a substance is handled that would be objectionable but no hazardous to health if introduced into the potable water system.
(a) DCs must be sized to provide an adequate supply of water and pressure for premises being served. Consult manufacturer's specifications for specific performance data.
(b) Premises where an uninterrupted water supply is critical should be provided with two assemblies installed in parallel. Assemblies should be sized in such a manner that either assembly will provide the minimum water requirements while the two together will provide the maximum flow required.
(c) The assembly shall be readily accessible with adequate room for testing and maintenance. DCs may be installed below grade, providing all test cocks are fitted with brass pipe plugs. All vaults shall be well drained, constructed of suitable materials, and sized to allow for the minimum clearances established below.
(d) Assemblies 2 inches and smaller shall have at least 6 inch clearance below and on both sides of the assembly and, if located in a vault, the bottom of the assembly shall be not more than 24 inches below grade. All assemblies larger than 2 inches shall have a minimum clearance of 12 inches on the back side, 24 inches on the test cock side, and 12 inches below the assembly. Headroom of 6 feet 0 inches is required in vaults without a fully removable top. A minimum access opening of 36 inches is required on all vault lids. "Y" pattern double check valve assemblies shall be installed so that the checks are horizontal and the test cocks face upward. These clearance standards apply to all assemblies installed in vaults, enclosures, and meter boxes.
(e) Vertical installations of DCs are allowed only on sizes up to and including 4 inches that meet the following requirements:
1. Internally spring-loaded check valves;
2. Flow is upward through assembly;
3. Manufacturer states their assembly can be used in a vertical position; and
4. Approved by the regulatory authority.
(f) All DCs must be tested in accordance with this article. Tests are the responsibility of the assembly owner. The owner must notify the regulatory authority upon installation of any backflow prevention assembly.
(g) Variances from these specifications will be evaluated on a case-by-case basis. Any deviations must have prior written approval of the regulatory authority.
(4) Double check detector backflow prevention assemblies (DCDA). May be utilized in all installations requiring a double check valve assembly and detector metering.
(a) DCDAs shall comply with the installation requirements applicable for double check valve assemblies (DCs).
(b) The line-size DC assembly and the bypass DC assembly must each be tested. A separate test report for each assembly must be completed by the certified tester.
(5) Pressure vacuum breaker backflow prevention assemblies (PVB). May be utilized at point-of-use protection only and where a substance is handled that would be objectionable but not hazardous to health if introduced into the potable water system. PVBs protect against backsiphonage only and shall not be installed where there is a potential for backpressure.
(a) Assembly shall be installed a minimum of 12 inches above highest downstream piping.
(b) PVBs shall not be installed in an area subject to flooding or where damage would occur from water discharge.
(c) The assembly shall be readily accessible for testing and maintenance, with a minimum clearance of 12 inches all around the assembly.
(d) All PVBs must be tested in compliance with this article. Tests are the responsibility of the assembly owner. The owner must notify the regulatory authority of installation of any backflow prevention assembly.
(e) Variances from these specifications will be evaluated on a case-by-case basis. Any deviations must have prior written approval of the regulatory authority.
(6) Spill resistant pressure vacuum breaker backflow prevention assemblies (SVB). May be utilized in all installations requiring a pressure vacuum breaker.
(a) SVBs shall comply with the installation requirements applicable for pressure vacuum breaker backflow prevention assemblies.
(M) Air gap separation. Air gaps provide maximum protection from backflow hazards and should be utilized at all locations where "high" hazardous substances are at risk of entering the potable water system.
(1) An air gap separation shall be at least twice the diameter of the supply pipeline measured vertically above the top rim of the receiving vessel and in no case less than one inch. If splashing is a problem, tubular screens may be attached or the supply line may be cut at a 45° angle. The air gap distance is measured from the bottom of the angle. Hoses are not allowed.
(2) Air gap separations shall not be altered in any way without prior approval from the regulatory authority and must be available for inspection at all reasonable times.
(3) Side walls, ribs or similar obstructions do not affect air gaps when spaced from the inside edge of the spout opening a distance greater than three times the diameter of the effective opening for a single, or a distance greater than four times the effective opening for two intersecting walls.
(N) Fire suppression systems. All new installations of fire suppression systems which utilize the city's potable water supply shall have installed an approved backflow prevention device. An approved double check detector backflow prevention assembly (DCDA) or reduced pressure detector assemblies (RPDA) shall be the minimum protection for fire sprinkler systems using piping material that is not approved for potable water use and/or that does not provide for periodic flow-through during each 24 hour period, unless a variance has been issued in writing from the regulatory authority. A RPDA must be installed if any solution other than the potable water can be introduced into the sprinkler system.
(1) It is the responsibility of all property owners and persons in charge of any premises to abide by the conditions of this section. In the event of any changes to the plumbing system, it is the responsibility of the property owners to notify the regulatory authority. All costs associated with this section and the purchase, installation, testing and repair of a DCDA or RPDA device is the responsibility of the property owner and persons in charge of any premises.
(2) Upon the approved installation of the DCDA or RPDA device, a cross-connection test report completed by a licensed fireline tester must be sent to the attention of the regulatory authority or his representative and include the information required by this section.
(O) Hydrant protection. An approved double check device backflow prevention assembly (DCD) shall be the minimum protection for fire hydrant water meters which are being used for a temporary water supply during any construction or other uses which would pose a potential hazard to the public water supply. An air gap must be provided, or an Atmospheric Vacuum Breaker assembly must be installed if any solution other than the potable water can be introduced into the water system.
(1) It is the responsibility of all persons engaging in the use and rental of a fire hydrant water meter to abide by the conditions of this section. All fire hydrant water meter rentals shall meet the current requirements as provided for by the Utility Billing Department.
(2) Only city fire hydrant water meters with approved backflow prevention assemblies are allowed to be used within the city limits.
(3) A refundable deposit is required to insure the return of all water meter and backflow assemblies to the Utility Customer Service Division. Failure to return the assemblies can result in the forfeiture of deposit and/or enforcement action being taken against the responsible party, as allowed for in the penalty section of this chapter.
(4) All non-approved fire hydrant meters which are found to be in use in the city will be confiscated and enforcement action taken against the responsible party, as allowed for in the enforcement subsection of this section.
(P) Responsibilities.
(1) Property owner. It is the responsibility of all property owners and/or persons in charge of any premises to abide by the conditions of this section and to comply with the following:
(a) Payment of all costs associated with this section and the purchase, installation, testing and repair of backflow prevention assemblies;
(b) To be installed and maintain all backflow prevention assemblies in accordance with this article and acceptable industry practice;
(c) All premises, business, or dwellings classified as "hazardous" shall cause to have all backflow prevention assemblies on their premises tested annually. Such testing must be conducted by a certified cross-connection tester who is registered with the city.
(d) Maintain all backflow prevention assemblies in proper working order at all times, including repair as required;
(e) Maintain all backflow prevention assemblies in a manner which allows them to be tested by a method that has been approved by the regulatory authority; and
(f) All records related to backflow prevention assembly installation, testing and repair shall be maintained on the premises for a minimum of three years.
(2) Certified backflow prevention assembly tester. Shall comply with the following requirements:
(a) Annually register with the regulatory authority;
(b) Maintain testing equipment in proper working condition/calibration;
(c) Maintain the design or operation characteristics of an assembly;
(d) Ensure that devices are tested according to accepted industry practice and TNRCC regulations;
(e) Enter required testing data, including test gauge serial numbers, on cross-connection test forms obtained from the regulatory authority;
(f) Provide a copy of the completed test report to the regulatory authority within 30 days of testing;
(g) Provide a copy of the completed test report to the property owners and/or person in charge of premises;
(h) Maintain testing and/or repair records for a minimum of three years.
(3) Regulatory authority. Shall comply with the following requirements:
(a) Authority to enter premises and install assembly(s) in cases of noncompliance and add the costs to the water service charges;
(b) Authority to terminate the water service in case of noncompliance;
(c) Shall inspect and cause to be tested all backflow prevention assemblies installed pursuant to the requirements of this section;
(d) Cause to be tested annually all backflow devices on premises that are classified as a health hazard location;
(e) Maintain all records related to backflow prevention assembly installation, testing and repair for a minimum of three years;
(f) Maintain accurate list of all registered installers and testers;
(g) Ensure that all new facilities are not provided with permanent water service until all backflow prevention assemblies have been tested and are operational;
(h) Except in cases where the testing of backflow prevention assemblies must be delayed until the installation of internal production or auxiliary equipment, the regulatory authority shall not approve a certificate of occupancy until all backflow prevention assemblies have been tested and are operational;
(i) The city shall not be liable for damage caused to any backflow prevention assembly as a result of the inspection or testing; and
(j) Maintain customer services inspection reports for 10 years.
(Q) Backflow prevention assembly tester certification registration required. Only approved TCEQ licensed backflow prevention assembly testers can test in the city. Testers must register annually with the regulatory authority, provide proof of TCEQ certification, provide proof that testing equipment is able to maintain a calibration of plus or minus 0.2 psid accuracy. Tester must also submit copy of any underlying license (i.e. plumber, irrigator, water operator, etc.).
(R) Compliance for lawn irrigation. All lawn irrigation systems must comply with requirements as stated in § 150.047.
(S) Beverage dispensers. The water supply connection to carbonated beverage dispensers shall be protected against backflow by a reduced pressure zone backflow assembly conforming to ASSE 1013.
(T) Mobile units. The connection of a mobile unit to any potable water system is prohibited unless such connection is protected by an air gap or an approved backflow prevention assembly. Prior approval and annual device testing of any backflow prevention assembly must be received from the regulatory authority before connecting to any potable water system.
(U) Enforcement.
(1) Violations.
(a) A person commits an offense if he fails to maintain backflow prevention assemblies in compliance with this section.
(b) A person commits an offense if he fails to comply with a repair order issued by the regulatory authority.
(c) A person commits an offense if backflow from premises he owns, operates or manages enters the public water supply system.
(d) A person commits an offense if he fails to pay any fees required by this section.
(e) A person commits an offense if he violates any part of this section.
(f) A person commits an offense if he reinstates water service to premises discontinued or disconnected under this article, except as directed by the regulatory authority.
(g) A person in charge of any facility commits an offense if he allows an unregistered tester to perform testing work at their establishment.
(h) A person commits an offense if he tests backflow prevention assembly within the city without being registered with the regulatory authority.
(i) A person commits an offense if he tests backflow prevention assembly within the city without being certified by the TNRCC.
(j) A person commits an offense if they fail to call for the required inspections.
(2) Penalty.
(a) A person who violates any provision of this section is guilty of a misdemeanor and upon conviction is punishable as set forth in § 10.99, for each act of violation and for each day or part of day during which the violation is committed, continued or permitted.
(b) In addition to proceeding under the authority of subsection (B)(1) of this section, the city is entitled to pursue all other criminal and civil remedies to which it is entitled under authority of statutes or other ordinances against a person committing any violation of this section.
(3) Sanction for failure to pay inspection fees. In addition to sanctions provided for by this section, the city is entitled to exercise sanctions provided for by other ordinances of the city.
(4) A certified testers' registration may be reviewed and revoked by the city if the regulatory authority determines that the tester:
(a) Has falsely, incompletely, or inaccurately reported assembly reports;
(b) Has used inaccurate gauges;
(c) Has used improper testing procedures; or
(d) Has created a threat to public health or the environment.
(Ord. 9-1998-54, passed 9-8-98; Am. Ord. 11-2008-80, passed 11-25-08)
(A) No plumbing work shall be done prior to obtaining a plumbing permit from the Building Inspections Department. Requests for permits may be made in person or by calling (817) 645-0955. All plumbing work shall be done in accordance with the rules and regulations as set forth in this chapter and the contractor or master plumber shall comply in all respects with the provisions of this subchapter.
(B) Payment shall be made of any and all fees that may become due and owing by the contractor or master plumber. These fees may be billed to the contractor and paid by the tenth of the following month, providing there is a signed authorization in the Building Inspections Office listing all personnel authorized to call for permits in the name of the company. A $25 late fee shall be assessed to all accounts not current by the tenth of the following month. Any account past due more than 60 days will lose all billing rights for six months, and no permits shall be issued until the account is paid in full.
(Ord. 3-2002-16, passed 3-26-02) Penalty, see § 150.999
(A) Requests for inspections. All inspection requests must be called in at least 24 hours prior to the inspection. Requests should be called in to the Inspections Hotline at (817) 556-8810 and can be made 24 hours a day. Any inspection properly called in before midnight shall be scheduled for the next workday. Inspection requests must include the address, plumbing contractor, permit number and type of inspection. Emergency inspections such as gas tests, open sewer lines, etc., can be made the same day. Call (817) 645-0955 for emergency inspections only.
(B) Failed/cancelled inspections. Inspections that fail, are not ready, or are cancelled will be required to call in again to the inspection hotline. Inspection cancellations must be called in to the hotline before 8:00 a.m. A re-inspection fee will be charged for all failed inspections, or inspections not ready by the third request.
(Ord. 3-2002-16, passed 3-26-02)
(A) Definitions. The following words and terms, when used in this section, have the following meanings, unless the context clearly indicates otherwise.
AIR GAP. A complete physical separation between the free flowing discharge end of a potable water supply pipeline and an open or non-pressure receiving vessel.
ATMOSPHERIC VACUUM BREAKER. An assembly containing an air inlet valve, a check seat, and an air inlet port. The flow of water into the body causes the air inlet valve to close the air inlet port. When the flow of water stops the air inlet valve falls and forms a check against back-siphonage. At the same time it opens the air inlet port allowing air to enter and satisfy the vacuum. Also known as an ATMOSPHERIC VACUUM BREAKER BACK-SIPHONAGE PREVENTION ASSEMBLY.
BACKFLOW PREVENTION. The mechanical prevention of reverse flow, or back siphonage, of non-potable water from an irrigation system into the potable water source.
BACKFLOW PREVENTION ASSEMBLY. Any assembly used to prevent backflow into a potable water system. The type of assembly used is based on the existing or potential degree of health hazard and backflow condition.
COMPLETION OF IRRIGATION SYSTEM INSTALLATION. When the landscape irrigation system has been installed, all minimum standards met, all tests performed, and the irrigator is satisfied that the system is operating correctly.
CONSULTING. The act of providing advice, guidance, review or recommendations related to landscape irrigation systems.
CROSS-CONNECTION. An actual or potential connection between a potable water source and an irrigation system that may contain contaminates or pollutants or any source of water that has been treated to a lesser degree in the treatment process.
DESIGN. The act of determining the various elements of a landscape irrigation system that will include, but not be limited to, elements such as collecting site specific information, defining the scope of the project, defining plant watering needs, selecting and laying out emission devices, locating system components, conducting hydraulics calculations, identifying any local regulatory requirements, or scheduling irrigation work at a site. Completion of the various components will result in an irrigation plan.
DESIGN PRESSURE. The pressure that is required for an emission device to operate properly. Design pressure is calculated by adding the operating pressure necessary at an emission device to the total of all pressure losses accumulated from an emission device to the water source.
DOUBLE CHECK VALVE. An assembly that is composed of two independently acting, approved check valves, including tightly closed resilient seated shutoff valves attached at each end of the assembly and fitted with properly located resilient seated test cocks. Also known as a DOUBLE CHECK VALVE BACKFLOW PREVENTION ASSEMBLY.
EMISSION DEVICE. Any device that is contained within an irrigation system and that is used to apply water. Common emission devices in an irrigation system include, but are not limited to, spray and rotary sprinkler heads, and drip irrigation emitters.
EMPLOYED. Engaged or hired to provide consulting services or perform any activity relating to the sale, design, installation, maintenance, alteration, repair, or service to irrigation systems. A person is employed if that person is in an employer-employee relationship as defined by Internal Revenue Code, 26 United States Code Service, § 3212(d) based on the behavioral control, financial control, and the type of relationship involved in performing employment related tasks.
HEAD-TO-HEAD SPACING. The spacing of spray or rotary heads equal to the manufacturer's published radius of the head.
HEALTH HAZARD. A cross-connection or potential cross-connection with an irrigation system that involves any substance that may, if introduced into the potable water supply, cause death or illness, spread disease, or have a high probability of causing such effects.
HYDRAULICS. The science of dynamic and static water; the mathematical computation of determining pressure losses and pressure requirements of an irrigation system.
INSPECTOR. A licensed plumbing inspector, water district operator, other governmental entity, or irrigation inspector who inspects irrigation systems and performs other enforcement duties for a municipality or water district as an employee or as a contractor.
INSTALLER. A person who actually connects an irrigation system to a private or public raw or potable water supply system or any water supply, who is licensed according to Texas Administrative Code, Title 30, Chapter 30 (relating to occupational licenses and registrations).
IRRIGATION INSPECTOR. A person who inspects irrigation systems and performs other enforcement duties for a municipality or water district as an employee or as a contractor and is required to be licensed under Texas Administrative Code, Title 30, Chapter 30 (relating to occupational licenses and registrations).
IRRIGATION PLAN. A scaled drawing of a landscape irrigation system which lists required information, the scope of the project, and represents the changes made in the installation of the irrigation system.
IRRIGATION SERVICES. Selling, designing, installing, maintaining, altering, repairing, servicing, permitting, providing consulting services regarding, or connecting an irrigation system to a water supply.
IRRIGATION SYSTEM. An assembly of component parts that is permanently installed for the controlled distribution and conservation of water to irrigate any type of landscape vegetation in any location, and/or to reduce dust or control erosion. This term does not include a system that is used on or by an agricultural operation as defined by Tex. Agricultural Code § 251.002.
IRRIGATION TECHNICIAN. A person who works under the supervision of a licensed irrigator to install, maintain, alter, repair, service or supervise installation of an irrigation system, including the connection of such system in or to a private or public, raw or potable water supply system or any water supply, and who is required to be licensed under Texas Administrative Code, Title 30, Chapter 30 (relating to occupational licenses and registrations).
IRRIGATION ZONE. A subdivision of an irrigation system with a matched precipitation rate based on plant material type (such as turf, shrubs, or trees), microclimate factors (such as sun/shade ratio), topographic features (such as slope) and soil conditions (such as sand, loam, clay, or combination) or for hydrological control.
IRRIGATOR. A person who sells, designs, offers consultations regarding, installs, maintains, alters, repairs, services or supervises the installation of an irrigation system, including the connection of such system to a private or public, raw or potable water supply system or any water supply, and who is required to be licensed under Texas Administrative Code, Title 30, Chapter 30.
IRRIGATOR-IN-CHARGE. The irrigator responsible for all irrigation work performed by an exempt business owner, including, but not limited to obtaining permits, developing design plans, supervising the work of other irrigators or irrigation technicians, and installing, selling, maintaining, altering, repairing, or servicing a landscape irrigation system.
LANDSCAPE IRRIGATION. The science of applying the necessary amount of water to promote or sustain healthy growth of plant material or turf.
LICENSE. An occupational license that is issued by the commission under Texas Administrative Code, Title 30, Chapter 30 to an individual that authorizes the individual to engage in an activity that is covered by Texas Administrative Code, Title 30, Chapter 30.
MAINLINE. A pipe within an irrigation system that delivers water from the water source to the individual zone valves.
MAINTENANCE CHECKLIST. A document made available to the irrigation system's owner or owner's representative that contains information regarding the operation and maintenance of the irrigation system, including, but not limited to: checking and repairing the irrigation system, setting the automatic controller, checking the rain or moisture sensor, cleaning filters, pruning grass and plants away from irrigation emitters, using and operating the irrigation system, the precipitation rates of each irrigation zone within the system, any water conservation measures currently in effect from the water purveyor, the name of the water purveyor, a suggested seasonal or monthly watering schedule based on current evapotranspiration data for the geographic region, and the minimum water requirements for the plant material in each zone based on the soil type and plant material where the system is installed.
MAJOR MAINTENANCE, ALTERATION, REPAIR, OR SERVICE. Any activity that involves opening to the atmosphere the irrigation main line at any point prior to the discharge side of any irrigation zone control valve. This includes, but is not limited to, repairing or connecting into a main supply pipe, replacing a zone control valve, or repairing a zone control valve in a manner that opens the system to the atmosphere.
MASTER VALVE. A remote control valve located after the backflow prevention device that controls the flow of water to the irrigation system mainline.
MATCHED PRECIPITATION RATE. The condition in which all sprinkler heads within an irrigation zone apply water at the same rate.
NEW INSTALLATION. An irrigation system installed at a location where one did not previously exist.
NON-HEALTH HAZARD. A cross-connection or potential cross-connection from a landscape irrigation system that involves any substance that generally would not be a health hazard but would constitute a nuisance or be aesthetically objectionable if introduced into the potable water supply.
NON-POTABLE WATER. Water that is not suitable for human consumption. Non-potable water sources include, but are not limited to, irrigation systems, lakes, ponds, streams, and gray water that is discharged from washing machines, dishwashers or other appliances, water vapor condensate from cooling towers, reclaimed water, and harvested rainwater.
PASS-THROUGH CONTRACT. A written contract between a contractor or builder and a licensed irrigator or exempt business owner to perform part or all of the irrigation services relating to an irrigation system.
POTABLE WATER. Water that is suitable for human consumption.
PRESSURE VACUUM BREAKER. An assembly containing an independently operating internally loaded check valve and an independently operating loaded air inlet valve located on the discharge side of the check valve. Also known as a PRESSURE VACUUM BREAKER BACK-SIPHONAGE PREVENTION ASSEMBLY.
RECLAIMED WATER. Domestic or municipal wastewater which has been treated to a quality suitable for beneficial use, such as landscape irrigation.
RECORDS OF LANDSCAPE IRRIGATION ACTIVITIES. The irrigation plans, contracts, warranty information, invoices, copies of permits, and other documents that relate to the installation, maintenance, alteration, repair, or service of a landscape irrigation system.
REDUCED PRESSURE PRINCIPLE BACKFLOW PREVENTION ASSEMBLY. An assembly containing two independently acting approved check valves together with a hydraulically operating mechanically independent pressure differential relief valve located between the two check valves and below the first check valve.
STATIC WATER PRESSURE. The pressure of water when it is not moving.
SUPERVISION. The on-the-job oversight and direction by a licensed irrigator who is fulfilling his or her professional responsibility to the client and/or employer in compliance with local or state requirements. Also a licensed installer working under the direction of a licensed irrigator or beginning January 1, 2009, an irrigation technician who is working under the direction of a licensed irrigator to install, maintain, alter, repair or service an irrigation system.
WATER CONSERVATION. The design, installation, service, and operation of an irrigation system in a manner that prevents the waste of water, promotes the most efficient use of water, and applies the least amount of water that is required to maintain healthy individual plant material or turf, reduce dust, and control erosion.
ZONE FLOW. A measurement, in gallons per minute or gallons per hour, of the actual flow of water through a zone valve, calculated by individually opening each zone valve and obtaining a valid reading after the pressure has stabilized. For design purposes, the zone flow is the total flow of all nozzles in the zone at a specific pressure.
ZONE VALVE. An automatic valve that controls a single zone of a landscape irrigation system.
(B) Valid license required.
(1) Any person who connects an irrigation system to the water supply within the city must hold a valid license, as defined by Texas Administrative Code Title 30, Chapter 30 and required by Tex. Occupations Code Ch. 1903.
(2) Exception: A property owner is not required to be licensed in accordance with Tex. Occupations Code, Title 12, § 1903.002(c)(1) if he or she is performing irrigation work in a building or on a premises owned or occupied by the person as the person's home. A home or property owner who installs an irrigation system must meet the standards contained in Texas Administrative Code, Title 30, Chapter 344 regarding spacing, water pressure, spraying water over impervious materials, rain or moisture shut-off devices or other technology, and isolation valves. If installation is performed by a homeowner, the required backflow device must be tested by a licensed backflow prevention tester.
(C) Permit required. Any person installing an irrigation system within the territorial limits of the city is required to obtain a permit from the Building Inspection Department. Any plan approved for a permit must be in compliance with the requirements of this section. An irrigation permit must be obtained prior to the beginning of any installation. The permit may be obtained upon approval of the irrigation plan, the submittal of a permit application, and payment of the permit fee as adopted by the current fee schedule of § 150.016.
(D) Backflow prevention methods and devices.
(1) Any irrigation system that is connected to the potable water supply must be connected through a backflow prevention method approved by the Texas Commission on Environmental Quality (TCEQ). The backflow prevention device must be approved by the American Society of Sanitary Engineers; or the Foundation for Cross-Connection Control and Hydraulic Research, University of Southern California; or the Uniform Plumbing Code; or any other laboratory that has equivalent capabilities for both the laboratory and field evaluation of backflow prevention assemblies. The backflow prevention device must be installed in accordance with the laboratory approval standards or if the approval does not include specific installation information, the manufacturer's current published recommendations.
(2) Where there are no conditions that present a health hazard, double check valve backflow prevention assemblies may be used to prevent backflow if the device is tested upon installation and tested annually:
(a) Backpressure caused by an elevation of pressure in the discharge piping by pump or elevation of piping above the supply pressure which could cause a reversal of the normal flow of water or back-siphonage conditions caused by a reduced or negative pressure in the irrigation system exist; and
(b) Test cocks are used for testing only.
(3) If a double check valve is installed below ground:
(a) Test cocks must be plugged, except when the double check valve is being tested;
(b) Test cock plugs must be threaded, water-tight, and made of non-ferrous material;
(c) A y-type strainer is installed on the inlet side of the double check valve;
(d) There must be a clearance between any fill material and the bottom of the double check valve to allow space for testing and repair; and
(e) There must be space on the side of the double check valve to test and repair the double check valve.
(4) If conditions that present a health hazard exist, a reduced pressure principle backflow prevention assemblies must be used if:
(a) The device is installed at a minimum of 12 inches above ground in a location that will ensure that the assembly will not be submerged; and
(b) Drainage is provided for any water that may be discharged through the assembly relief valve.
(5) Backflow prevention devices used in applications designated as health hazards must be tested upon installation and annually thereafter.
(6) If an irrigation system is connected to a potable water supply through a double check valve, pressure vacuum breaker, or reduced pressure principle backflow assembly and includes an automatic master valve on the system, the automatic master valve must be installed on the discharge side of the backflow prevention assembly.
(7) The irrigator shall ensure the backflow prevention device is tested prior to being placed in service and annually. All test results must be provided to the city's Inspection Department and within ten business days of testing of the backflow prevention device.
(E) Specific conditions and cross-connection control.
(1) Before any chemical is added to an irrigation system connected to the potable water supply, the irrigation system must be connected through a reduced pressure principle backflow prevention assembly.
(2) Connection of any additional water source to an irrigation system that is connected to the potable water supply can only be done if the irrigation system is connected to the potable water supply through a reduced-pressure principle backflow prevention assembly.
(3) Irrigation system components with chemical additives induced by aspiration, injection, or emission system connected to any potable water supply must be connected through a reduced pressure principle backflow device.
(4) If an irrigation system is designed or installed on a property that is served by an on-site sewage facility, as defined in Texas Administrative Code, Title 30, Chapter 285 then:
(a) All irrigation piping and valves must meet the separation distances from the on-site sewage facilities system as required for a private water line in Texas Administrative Code, Title 30, § 285.91(10);
(b) Any connections using a private or public potable water source that is not the city's potable water system must be connected to the water source through a reduced pressure principle backflow prevention assembly as defined in Texas Administrative Code, Title 30, § 344.50; and
(c) Any water from the irrigation system that is applied to the surface of the area utilized by the on-site sewage facility system must be controlled on a separate irrigation zone or zones so as to allow complete control of any irrigation to that area so that there will not be excess water that would prevent the on-site sewage facilities system from operating effectively.
(F) Water conservation. All irrigation systems shall be designed, installed, maintained, altered, repaired, serviced, and operated in a manner that will promote water conservation as defined in the definitions division of this section.
(G) Irrigation plan design: minimum standards.
(1) An irrigator shall prepare an irrigation plan for each site where a new irrigation system will be installed. A paper or electronic copy of the irrigation plan must be on the job site at all times during the installation of the irrigation system. A drawing showing the actual installation of the system is due to each irrigation system owner after all new irrigation system installations. During the installation of the irrigation system, variances from the original plan may be authorized by the licensed irrigator if the variance from the plan does not:
(a) Diminish the operational integrity of the irrigation system;
(b) Violate any requirements of this section; and
(c) Go unnoted in red on the irrigation plan.
(2) The irrigation plan must include complete coverage of the area to be irrigated. If a system does not provide complete coverage of the area to be irrigated, it must be noted on the irrigation plan.
(3) All irrigation plans used for construction must be drawn to scale. The plan must include, at a minimum, the following information:
(a) The irrigator's seal, signature, and date of signing;
(b) All major physical features and the boundaries of the areas to be watered;
(c) A north arrow;
(d) A legend;
(e) The zone flow measurement for each zone;
(f) Location and type of each:
1. Controller; and
2. Sensor (for example, but not limited to, rain, moisture, wind, flow, or freeze);
(g) Location, type, and size of each:
1. Water source, such as, but not limited to a water meter and point(s) of connection;
2. Backflow prevention device;
3. Water emission device, including, but not limited to, spray heads, rotary sprinkler heads, quick-couplers, bubblers, drip, or micro-sprays;
4. Valve, including but not limited to, zone valves, master valves, and isolation valves;
5. Pressure regulation component; and
6. Main line and lateral piping.
(h) The scale used; and
(i) The design pressure.
(H) Design and installation: minimum requirements.
(1) No irrigation design or installation shall require the use of any component, including the water meter, in a way which exceeds the manufacturer's published performance limitations for the component.
(2) Spacing.
(a) The maximum spacing between emission devices must not exceed the manufacturer's published radius or spacing of the device(s). The radius or spacing is determined by referring to the manufacturer's published specifications for a specific emission device at a specific operating pressure.
(b) New irrigation systems shall not utilize above-ground spray emission devices in landscapes that are less than 48 inches not including the impervious surfaces in either length or width and which contain impervious pedestrian or vehicular traffic surfaces along two or more perimeters. If pop-up sprays or rotary sprinkler heads are used in a new irrigation system, the sprinkler heads must direct flow away from any adjacent surface and shall not be installed closer than four inches from a hardscape, such as, but not limited to, a building foundation, fence, concrete, asphalt, pavers, or stones set with mortar.
(c) Narrow paved walkways, jogging paths, golf cart paths or other small areas located in cemeteries, parks, golf courses or other public areas may be exempted from this requirement if the runoff drains into a landscaped area.
(3) Water pressure. Emission devices must be installed to operate at the minimum and not above the maximum sprinkler head pressure as published by the manufacturer for the nozzle and head spacing that is used. Methods to achieve the water pressure requirements include, but are not limited to, flow control valves, a pressure regulator, or pressure compensating spray heads.
(4) Piping. Piping in irrigation systems must be designed and installed so that the flow of water in the pipe will not exceed a velocity of five feet per second for polyvinyl chloride (PVC) pipe.
(5) Irrigation zones. Irrigation systems shall have separate zones based on plant material type, microclimate factors, topographic features, soil conditions, and hydrological requirements.
(6) Matched precipitation rate. Zones must be designed and installed so that all of the emission devices in that zone irrigate at the same precipitation rate.
(7) Irrigation systems shall not spray water over surfaces made of concrete, asphalt, brick, wood, stones set with mortar, or any other impervious material, such as, but not limited to, walls, fences, sidewalks, streets, etc.
(8) Master valve. When provided, a master valve shall be installed on the discharge side of the backflow prevention device on all new installations.
(9) PVC pipe primer solvent. All new irrigation systems that are installed using PVC pipe and fittings shall be primed with a colored primer prior to applying the PVC cement in accordance with the Uniform Plumbing Code (Section 316) or the International Plumbing Code (Section 605).
(10) Rain or moisture shut-off devices or other technology. All new automatically controlled irrigation systems must include sensors or other technology designed to inhibit or interrupt operation of the irrigation system during periods of moisture or rainfall. Rain or moisture shut-off technology must be installed according to the manufacturer's published recommendations. Repairs to existing automatic irrigation systems that require replacement of an existing controller must include a sensor or other technology designed to inhibit or interrupt operation of the irrigation system during periods of moisture or rainfall.
(11) Isolation valve. All new irrigation systems must include an isolation valve between the water meter and the backflow prevention device.
(12) Depth coverage of piping. Piping in all irrigation systems must be installed according to the manufacturer's published specifications for depth coverage of piping.
(a) If the manufacturer has not published specifications for depth coverage of piping, the piping must be installed to provide minimum depth coverage of six inches of select backfill, between the top of the pipe and the natural grade of the topsoil. All portions of the irrigation system that fail to meet this standard must be noted on the irrigation plan. If the area being irrigated has rock at a depth of six inches or less, select backfill may be mounded over the pipe. Mounding must be noted on the irrigation plan and discussed with the irrigation system owner or owner's representative to address any safety issues.
(b) If a utility, man-made structure or roots create an unavoidable obstacle, which makes the six-inch depth coverage requirement impractical, the piping shall be installed to provide a minimum of two inches of select backfill between the top of the pipe and the natural grade of the topsoil.
(c) All trenches and holes created during installation of an irrigation system must be backfilled and compacted to the original grade.
(13) Wiring irrigation systems.
(a) Underground electrical wiring used to connect an automatic controller to any electrical component of the irrigation system must be listed by Underwriters Laboratories as acceptable for burial underground.
(b) Electrical wiring that connects any electrical components of an irrigation system must be sized according to the manufacturer's recommendation.
(c) Electrical wire splices which may be exposed to moisture must be waterproof as certified by the wire splice manufacturer.
(d) Underground electrical wiring that connects an automatic controller to any electrical component of the irrigation system must be buried with a minimum of six inches of select backfill.
(14) Water contained within the piping of an irrigation system is deemed to be non-potable. No drinking or domestic water usage, such as, but not limited to, filling swimming pools or decorative fountains, shall be connected to an irrigation system. If a hose bib (an outdoor water faucet that has hose threads on the spout) is connected to an irrigation system for the purpose of providing supplemental water to an area, the hose bib must be installed using a quick coupler key on a quick coupler installed in a covered purple valve box and the hose bib and any hoses connected to the bib must be labeled "non potable, not safe for drinking." An isolation valve must be installed upstream of a quick coupler connecting a hose bib to an irrigation system.
(15) Beginning January 1, 2010, either a licensed irrigator or a licensed irrigation technician shall be on-site at all times while the landscape irrigation system is being installed. When an irrigator is not onsite, the irrigator shall be responsible for ensuring that a licensed irrigation technician is on-site to supervise the installation of the irrigation system.
(I) Completion of irrigation system installation. Upon completion of the irrigation system, the irrigator or irrigation technician who provided supervision for the on-site installation shall be required to complete four items:
(1) A final "walk through" with the irrigation system's owner or the owner's representative to explain the operation of the system;
(2) The maintenance checklist on which the irrigator or irrigation technician shall obtain the signature of the irrigation system's owner or owner's representative and shall sign, date, and seal the checklist. If the irrigation system's owner or owner's representative is unwilling or unable to sign the maintenance checklist, the irrigator shall note the time and date of the refusal on the irrigation system's owner or owner's representative's signature line. The irrigation system owner or owner's representative will be given the original maintenance checklist and a duplicate copy of the maintenance checklist shall be maintained by the irrigator. The items on the maintenance checklist shall include but are not limited to:
(a) The manufacturer's manual for the automatic controller, if the system is automatic;
(b) A seasonal (spring, summer, fall, winter) watering schedule based on either current/real time evapotranspiration or monthly historical reference evapotranspiration (historical ET) data, monthly effective rainfall estimates, plant landscape coefficient factors, and site factors;
(c) A list of components, such as the nozzle, or pump filters, and other such components, that require maintenance and the recommended frequency for the service; and
(d) The statement, "This irrigation system has been installed in accordance with all applicable state and local laws, ordinances, rules, regulations or orders. I have tested the system and determined that it has been installed according to the Irrigation Plan and is properly adjusted for the most efficient application of water at this time."
(3) A permanent sticker which contains the irrigator's name, license number, company name, telephone number and the dates of the warranty period shall be affixed to each automatic controller installed by the irrigator or irrigation technician. If the irrigation system is manual, the sticker shall be affixed to the original maintenance checklist. The information contained on the sticker must be printed with waterproof ink and include: irrigator's name, license number, company name, telephone number and the dates of the warranty period.
(4) The irrigation plan indicating the actual installation of the system must be provided to the irrigation system's owner or owner representative.
(J) Maintenance, alteration, repair, or service of irrigation systems.
(1) The irrigator is responsible for all work that the irrigator performed during the maintenance, alteration, repair, or service of an irrigation system during the warranty period. The irrigator or business owner is not responsible for the professional negligence of any other irrigator who subsequently conducts any irrigation service on the same irrigation system.
(2) All trenches and holes created during the maintenance, alteration, repair, or service of an irrigation system must be returned to the original grade with compacted select backfill.
(3) Colored PVC pipe primer solvent must be used on all pipes and fittings used in the maintenance, alteration, repair, or service of an irrigation system in accordance with the International Plumbing Code (Section 605).
(4) When maintenance, alteration, repair or service of an irrigation system involves excavation work at the water meter or backflow prevention device, an isolation valve shall be installed, if an isolation valve is not present.
(K) Reclaimed water. Reclaimed water may be utilized in landscape irrigation systems if:
(1) There is no direct contact with edible crops, unless the crop is pasteurized before consumption;
(2) The irrigation system does not spray water across property lines that do not belong to the irrigation system's owner;
(3) The irrigation system is installed using purple components;
(4) The domestic potable water line is connected using a reduced pressure principle backflow prevention device, in accordance with § 290.47(i) of this title (relating to Appendices);
(5) A minimum of an eight inch by eight inch sign, in English and Spanish, is prominently posted on/in the area that is being irrigated, that reads, "RECLAIMED WATER - DO NOT DRINK" and "AGUA DE RECUPERACIÓN - NO BEBER"; and
(6) Backflow prevention on the reclaimed water supply line shall be in accordance with the regulations of the city's water provider.
(L) Advertisement requirements.
(1) All vehicles used in the performance of irrigation installation, maintenance, alteration, repair, or service must display the irrigator's license number in the form of "LI_______" in a contrasting color of block letters at least two inches high, on both sides of the vehicle.
(2) All forms of written and electronic advertisements for irrigation services must display the irrigator's license number in the form of "LI_____." Any form of advertisement, including business cards and estimates which displays an entity's or individual's name other than that of the licensed irrigator must also display the name of the licensed irrigator and the licensed irrigator's license number. Trailers that advertise irrigation services must display the irrigator's license number.
(3) The name, mailing address, and telephone number of the commission must be prominently displayed on a legible sign and displayed in plain view of the purpose of addressing complaints at the permanent structure where irrigation business is primarily conducted and irrigation records are kept.
(M) Contracts.
(1) All contracts to install an irrigation system must be in writing and signed by each party and must specify the irrigator's name, license number, business address, current business telephone numbers, the date that each party signed the agreement, the total agreed price, and must contain the statement, "Irrigation in Texas is regulated by the Texas Commission on Environmental Quality (TCEQ), MC-178, PO Box 13087, Austin, Texas 78711-3087. TCEQ's website is: www.tceq.state.tx.us." All contracts must include the irrigator's seal, signature, and date.
(2) All written estimates, proposals, bids, and invoices relating to the installation or repair of an irrigation system(s) must include the irrigator's names, license number, business address, current business telephone number(s), and the statement: "Irrigation in Texas is regulated by the Texas Commission on Environmental Quality (TCEQ), MC-178, PO Box 13087, Austin, Texas 78711-3087. TCEQ's website is: www.tceq.state.tx.us."
(3) An individual who agrees by contract to provide irrigation services as defined in Texas Administrative Code, Title 30, § 344.30 (relating to license required) shall hold an irrigator license issued under Texas Administrative Code, Title 30, § 344.1(36) (relating to definitions). If a pass-through contract includes irrigation services, then the irrigation portion of the contract can only be performed by a licensed irrigator. If an irrigator installs a system pursuant to a pass-through contract, the irrigator shall still be responsible for providing the irrigation system's owner or owner's representative a copy of the warranty and all other documents required under this section. A pass-through contract must identify by name and license number the irrigator that will perform the work and must provide a mechanism for contracting the irrigator for irrigation system warranty work.
(4) The contract must include the dates that the warranty is valid.
(5) Warranties for systems:
(a) On all installations of new irrigation systems, an irrigator shall present the irrigation system's owner or owner's representatives with a written warranty covering materials and labor furnished in the new installation of the irrigator system. The irrigator shall be responsible for adhering to terms of warranty. If the irrigator's warranty is less than the manufacturer's warranty for the system components, then the irrigator shall provide the irrigation system's owner or the owner's representative with applicable information regarding the manufacturer's warranty period. The warranty must include the irrigator's seal, signature, and date. If the warranty is part of an irrigator's contract, a separate warranty document is not required.
(b) An irrigator's written warranty on new irrigation systems must specify the irrigator's name, business address, and business telephone numbers, must contain the signature of the irrigation system's owner or owner's representative confirming receipt of the warranty and must include the statement; "Irrigation in Texas is regulated by the Texas Commission on Environmental Quality (TCEQ), MC-178, PO Box 130897, Austin, Texas 78711-3087. TCEQ's website is: www.tceq.state.tx.us."
(c) On all maintenance, alterations, repairs, or service to existing irrigation systems, an irrigator shall present the irrigation system's owner or owner's representative a written document that identifies the materials furnished in the maintenance, alternation, repair, or service. If a warranty is provided, the irrigator shall abide by the terms. The warranty document must include the irrigator's name and business contact information.
(N) Duties and responsibilities of city irrigation inspectors. A licensed irrigation inspector shall enforce the ordinance of the city, and shall be responsible for:
(1) Verifying that the appropriate permits have been obtained for an irrigation system and that the irrigator and installer or irrigation technician, if applicable, are licensed;
(2) Inspecting the irrigation system;
(3) Determining that the irrigation system complies with the requirements of this section;
(4) Determining that the appropriate backflow prevention device was installed, tested, and test results provided to the city;
(5) Investigating complaints related to irrigation system installation, maintenance, alteration, repairs, or service of an irrigation system and advertisement of irrigation services; and
(6) Maintaining records according to this section.
(O) Items not covered by this section. Any item not covered by this section and required by law shall be governed by the Texas Occupations Code, the Texas Water Code, Title 30 of the Texas Administrative Code, and any other applicable state statute or TCEQ rule.
(P) Fees. The City Council may create a schedule of fees for obtaining and renewing an irrigation permit. These fees will be in amounts sufficient to cover the city's costs in issuing and renewing the permits, including, but not limited to, staff time and other overhead costs. All permit fees will be based up the currently adopted fee schedule in § 150.016.
(Q) Enforcement.
(1) The city shall have the power to administer and enforce the provisions of this section as may be required by governing law. Any person, firm, corporation or agent who shall violate a provision of this code, or fails to comply therewith, or with any of the requirements thereof, is subject to suit for injunctive relief as well as prosecution for criminal violations. Any violation of this section is declared to be a nuisance.
(2) Any person violating any provision of this section shall, upon conviction, be fined a sum not exceeding $2,000. Each day that a provision of this section is violated shall constitute a separate offense. An offense under this section is a Class C misdemeanor, punishable by a fine of up to $2,000.
(3) Nothing in this section shall be construed as a waiver of the city's right to bring a civil action to enforce the provisions of this section and to seek remedies as allowed by law, including, but not limited to the following:
(a) Injunctive relief to prevent specific conduct that violates this section or to require specific conduct that is necessary for compliance with this section; and
(b) Other available relief.
(Ord. 11-2008-79, passed 11-25-08)
Loading...