§ 151.61 ADDITIONAL REQUIREMENTS.
   (A)   All buildings shall have a readily accessible, visible external shutoff valve located at the building or tank for liquid or vapor fuels.
   (B)   All vents for combustible fuel appliances shall terminate a minimum of 35 inches above final grade.
   (C)   Flexible gas line connectors shall not be permitted for furnace and water heater. Exception: Manufacturer requirements or hanging units.
   (D)   Supply or return ducts and radon gas tubes shall be prohibited in an exterior wall and shall be installed in a minimum 2X6 interior wall, soffit or chase.
   (E)   804.3.4 Horizontal Terminations #6 to read 35" above finished grade not 12 inches.
(Ord. 1885, passed 2-20-17; Am. Ord. 2086, passed 5-16-22)