(A) This calculation for a 1,500-square-foot dwelling shall be made as follows.
General lighting load 1500 square feet by 3 = 4500 watts
4500 - 115 volts = 39.l amperes
(3-15 amp circuits)
(3-15 amp circuits)
Allowance for two appliance circuits = 3000 watts
(2 circuits-20 amps)
(2 circuits-20 amps)
Laundry circuit NEC 220-3(a) = 1500 watts
(l circuit-20 amps)
(l circuit-20 amps)
Net total = 9000 watts
(B) (1) Feeder demand factors.
First 3000 watts at 100% = 3000 watts
Remainder 6000 watts at 35% = 2100 watts
Net total = 5100 watts
12 kw range load (NEC Table 220-19) = 8000 watts
Net load with range = 13,100 watts
Utility installed 115/230 volt three-wire service.
(2) Example:
13,100 watts - 230 volts = amperes
NEC Section 230-41(b)(2) Net computed load exceeds 10 kw, so service conductors shall be at 100 amperes.
(Prior Code, § 152.36)