8.12.510 Appendix B.
   Appendix B, Table 105.2 of the California Fire Code is amended to read as follows.
   TABLE B105.2 - REQUIRED FIRE FLOW FOR BUILDINGS OTHER THAN ONE- AND TWO- FAMILY DWELLINGS, GROUP R-3 AND R-4 BUILDINGS AND TOWNHOUSES
 
AUTOMATIC SPRINKLER SYSTEM (Design Standard)
MINIMUM FIRE FLOW (gallons per minute)
FLOW DURATION (hours)
No automatic sprinkler system
Value in Table B105.1(2)
Duration in Table B105.1(2)
Section 903.3.1.1 California Fire Code
50% of the value in Table B105.1(2)a
Duration in Table B105.1(2) at the reduced flow rate
Section 903.3.1.2 of the California Fire Code
50% of the value in Table B105.1(2)b
Duration in Table B105.1(2) at the reduced flow rate
 
   For S1: 1 gallon per minute = 3.785 L/m.
   a. The reduced fire-flow shall not be less than 1,000 gallons per minute.
   b. The reduced fire-flow shall be not less than 1,500 gallons per minute.”