Section 907.1.6 is added to section 907 of the California Fire Code to read as follows:
“907.1.6 Fire alarm control panel. The main fire alarm control panel (FACP) shall be located in the same room as, and sharing the same access as the fire sprinkler riser. The FACP shall have a minimum 36 inches of face clearance and 6 inches side clearance from any other wall or equipment.”
(Ord. 227, passed 11-9-2022)