8.12.330 Fire hydrant size and outlets.
   Section 507.5.7 is added to Section 507 of the California Fire Code to read as follows:
   “507.5.7 Fire Hydrant size and outlets.
   As determined by the fire code official, fire hydrant sizes and outlets shall be based on the following:
      1.   Residential Standard - one (1) four (4) inch outlet and one (1) two and one-half (2 ½) inch outlet.
      2.   Super Hydrant Standard - one (1) four (4) inch outlet and two (2) two and one-half (2 ½) inch outlet.
      3.   Super Hydrant Enhanced - two (2) four (4) inch outlets and one (1) two and one-half (2 ½) inch outlet.”
(Ord. 190, passed 1-15-2020; Am. Ord. 213, passed 10-6-2021; Am. Ord. 227, passed 11-9-2022)