§ 118.05 CONSTRUCTION AND MAINTENANCE REQUIREMENTS.
   (A)   All sauna rooms and restrooms and bathrooms used in connection therewith shall be constructed of materials which are impervious to moisture, bacteria, mold and fungus growth. The floor-to-wall and wall-to-wall joists shall be constructed to provide a sanitary cove with a minimum radius of one inch. There shall be no locks on doors of sauna rooms nor on any other room in the licensed premises except on one business office, closets for the storage of supplies and toilet rooms.
   (B)   All toilet rooms used in connection with saunas shall be provided with mechanical ventilation with two cubic foot per minute per square foot of floor area, a minimum of 30 foot candles of illumination, a hand washing sink or sinks equipped with hot and cold running water under pressure, sanitary towels and soap dispenser.
   (C)   Each sauna shall have a janitor's closet which shall be provided for the storage of cleaning supplies. The closet shall have mechanical ventilation with two cubic foot per minute per square foot of floor area and a minimum of 30 foot candles of illumination. The closet shall include a mop sink.
   (D)   Floors, walls and equipment in sauna rooms, in restrooms and in bathrooms used in connection therewith must be kept in a state of good repair and clean at all times. Linens and other materials shall be stored at least 12 inches off the floor. Clean towels and wash cloths must be made available to each customer.
   (E)   Individual lockers shall be made available for use by patrons. The lockers shall have separate keys for locking.
   (F)   The premises shall contain adequate refuse receptacles, which shall be emptied at least daily.
(Prior Code, § 6.40, Subd. 5)