APPENDIX B
FOUNDATIONS
 
FOUNDATION SPECIFICATIONS
For Canfield Village Soil Types
GROUP NO. 1
(FAVORABLE SOILS) SLOPE 2 - 12%
Light color, moderately well drained soils, clay loam, sandy and gravelly glacial out wash, low medium shrink-swell, medium bearing depth to bed rock in excess of 6' - 0".
TYPE OF FOUNDATION
Minimum Code Requirements are:
Basement foundation walls shall use a minimum 10" block, crawl spaces and unexcavated areas must use a minimum 8" block.
Basement foundation walls shall have wall ties located every third course.
8" x 16" pilasters shall be located at 12' - 0" centers.
Footers for 8" block walls are 24" x 10" with two-5/8" rods and for 10" blocks walls are 26" x 10" with two-5/8" rods.
Foundation to be pargetted and W.P. painted.
Column pads - one story house 45" x 45" x 12" for two-story house 54" x 54" x 12" all pads maximum spacing 12" - 0". Chimney footers to be 12" projection on all sides.
All basement and crawl space foundations shall have complete footer drainage inside and outside of footer. Outside footer tile shall be backfilled with a porous material 18" wide from the tile to within 12" of finish grade.
Positive surface drainage must be achieved at all times from the building to meet existing grade.
Precast, insulated foundation systems shall be constructed with the footer requirements listed above. Wall thickness specifications must be included in a certified design by a registered professional engineer in the State of Ohio.
GROUP NO. II
(STEEP SOIL) SEVERE SLOPES 12 - 50%
Light color, well drained soils, clay loamed, formed glacial till, severe slope, slow shrink-swell potential, less than minimum bearing capacity.
 
TYPE OF FOUNDATION
 
Minimum Code Requirements are:
Basement foundation walls shall use as a minimum 10" block, crawl spaces and unexcavated areas must use as a minimum 8" block.
Basement foundation walls shall have wall ties located every third course.
8" x 16" pilasters shall be located at 12' - 0" centers.
Footers for 8" block walls are 24" x 10" with two-5/8" rods and for 10" blocks walls are 26" x 10" with two-5/8" rods.
Foundation to be pargetted and W.P. painted.
Maximum depth of basement from finish grade 7' - 0".
Column pads - one story house 45" x 45" x 12" for two-story house 54" x 54" x 12" all pads maximum spacing 12" - 0". Chimney footers to be 12" projection on all sides.
All basement and crawl space foundations shall have complete footer drainage inside and outside of footer. Outside footer tile shall be backfilled with a porous material 18" wide from the tile to within 12" of finish grade.
Positive surface drainage must be achieved at all times from the building to meet existing grade.
Precast, insulated foundation systems shall be constructed with the footer requirements listed above. Wall thickness specifications must be included in a certified design by a registered professional engineer in the State of Ohio.
GROUP NO. III
(SEASONALLY WET SOIL) SLOPE 0 - 6%
 
Light colored, poorly drained soil formed in loam glacial till or silty, sandy and gravelly glacial out-wash, seasonally highwater table, with perched water table during winter and spring, low to medium shrink-swell potential, little more than poor bearing.
 
TYPE OF FOUNDATION
 
Minimum Code requirements are:
Basement foundation walls shall use as minimum 10" block, crawl spaces and unexcavated areas must use as a minimum 8" block.
Basement foundation walls shall have wall ties located every third course.
   8" x 16" pilasters shall be located at 12' - 0" centers.
Foundation to be pargetted and W.P. painted.
Footers for one story house 26" x 10", with two-5/8" rods, for two story houses, footers are 26" x 10" with two-5/8" round rods.
Column pads - one story house 45" x 45" X 12" for two-story house 54" x 54" x 12" all pads maximum spacing 12" - 0". Chimney footers to be 12" projection on all sides.
All basement and crawl space foundations shall have complete footer drainage inside and outside of footer. Outside footer tile shall be backfilled with a porous material 18" wide from the tile to within 12" of finish grade.
Positive surface drainage must be achieved at all times from the building to meet existing grade.
Precast, insulated foundation systems shall be constructed with the footer requirements listed above. Wall thickness specifications must be included in a certified design by a registered professional engineer in the State of Ohio.
GROUP NO. IV
(WET SHRINK-SWELL SOILS) SLOPE 0 - 6%
 
Light or dark colored, poorly drained soils, extremely high water tables most all year formed in lucustrine deposits, clayey glacial till, sandy and gravelly glacial outwash, moderate to high shrink-swell potential, poor bearing.
 
TYPE OF FOUNDATION
Minimum Code requirements are:
Basement foundation walls shall use as a minimum 10" block, crawl spaces and unexcavated areas must use as a minimum 8" block.
Basement foundation walls shall have wall ties located every third course.
8" x 16" pilasters shall be located at 12' - 0" centers.
   Foundation to be pargetted and W.P. painted.
Footers for one story house, slab, crawl space or basement not exceeding 5'0" depth for frame or brick veneer type to be 26" x 10" with two-5/8" rods, for two story houses frame or brick veneer with basement to be 30" x 10" with two-5/8" round rods.
Column pads for one story house 50" x 50" x 12", for two story houses 63" x 63" x 12". All pads maximum spacing 12'. Chimney footers to be 12" projection on all sides.
All basement and crawl space foundations shall have complete footer drainage inside and outside of footer. Outside footer tile shall be backfilled with a porous material 18" wide from the tile to within 12" of finish grade.
Positive surface drainage must be achieved at all times from the building to meet existing grade.
Additional safety factor for foundation walls below 5' - 0" depths is to place Dur-O-Wall reinforcing at every third course (3 rows) with rodded walls.
Precast, insulated foundation systems shall be constructed with the footer requirements listed above.
ALTERNATE TYPE FOUNDATIONS:
8" Concrete poured foundation, keyed to footer with 2 5/8" round rods below the window openings around perimeter of foundation.
Poured foundations to be W.P. painted as required.
NOTE: Foundations exceeding 5' - 0" depth, concrete poured walls to have two rows of 5/8" round rods, two located about 3' - 0" above footer and 2 5/8" round rods located below window opening.
Block walls 8" or 10" type to have two rods of channel blocks with 2 5/8" round rods around perimeter of foundation at 5th course and top course grouted in place..... pilasters not over 12' - 0: spacing. Also foundation of 10-block walls and pilasters not over 12' - 0 spacing with all pilasters rodded with 2 - 5/8 round rods vertically or walls between pilasters rodded at center with 2 - 5/8 round rods.
Additional safety factor for foundation walls below 5' - 0 depths is to place Dur-O-Wall reinforcing at every third course (3 rows) with rodded walls.
(Ord. 2008-17. Passed 7-9-08.)
GROUP NO. V
(RESTRICTED SOIL)
 
   (a)   Light to dark colored, moderate to poorly drained soils in alluvium on flood plains, water table high most of year and subject to flooding.
 
   (b)   Severely limited for home site, questionable ground bearing for foundation.
 
LIMITATIONS
 
   Building any structure is not permitted in a designated 100-year flood plain. The elevation of the 100-year flood plain must be provided and certified by a State of Ohio registered professional engineer. The owner must provide a certified foundation design drawing by a State of Ohio registered professional engineer for building foundations outside of the 100-year flood plain for groups (a) and (b) above. To build on strip mine soil sub grade (b), bearing capacity tests and recommendations for type foundations are required, and shall be provided by State of Ohio registered professional engineer.