Exemptions: Agricultural Buildings, as defined in IBC Section 202, as amended, below, are exempt from the building codes adopted herein but shall remain subject to placement requirements established by zoning regulations.
IBC section 101.1, "Title" These regulations shall be known as the building code of the city of Caldwell, hereinafter referred to as "this code."
IRC section 101.1, "Title" These provisions shall be known as the residential code for one- and two-family dwellings of the city of Caldwell, and shall be cited as such and will be referred to herein as "this code."
Delete exception no. 2 contained under IRC section R101.2, "Scope," and replace with the following: Exception: The following shall also be permitted to be constructed in accordance with this code: 1. Owner-occupied lodging houses with five (5) or fewer guestrooms and ten (10) or fewer total occupants. 2. A care facility with five (5) or fewer persons receiving custodial care within a dwelling unit or single-family dwelling. 3. A care facility for five (5) or fewer persons receiving personal care that are within a dwelling unit or single-family dwelling. 4. A care facility with twelve (12) or fewer children receiving day care within a dwelling unit or single-family dwelling.
IBC section 101.4.3, "Plumbing" is deleted and repealed in its entirety.
IBC section 101.4.4, "Property Maintenance" is deleted and repealed along with all references to the international property maintenance code throughout the IBC and IRC.
IBC/IRC section 103.2, "Appointment" is deleted and repealed in its entirety.
IRC section R104.10.1, Flood hazard areas.
IBC section 105.1.1, "Annual Permit" is deleted and repealed in its entirety.
IBC section 105.1.2, "Annual Permit Records" is deleted and repealed in its entirety.
IBC/IRC section 105.2, the subsections therein entitled "Electrical" and "Plumbing" are deleted and repealed in their entirety.
Delete item no. 7 contained under the "building" subsection of IRC section R105.2, "Work Exempt From Permit" and replace with the following:
7. Prefabricated swimming pools that are not greater than four (4) feet (one thousand, two hundred nineteen (1219) mm) deep.
Add the following as item number 11 under the “Building” subheading of Section R105.2 Work exempt from permit:
11. Flag poles.
IBC/IRC section 105.3.2, "Time Limitation Of Application" is amended to read: Applications for permit shall be considered abandoned after 180 days from the filing date. The building official may discard any abandoned application, plans or documents without the granting of an extension when no efforts to contact the building department have been exercised by the applicant.
IBC/IRC section 106.5, "Retention Of Construction Documents" is deleted and repealed in its entirety.
IBC section 107.1, Submittal Documents. Submittal documents consisting of construction documents, statement of special inspections, geotechnical report and other data shall be submitted in two or more sets with each permit application. The construction documents shall be prepared by a registered design professional as defined in this code (§12-01-21). Where special conditions exist, the building official is authorized to require additional construction documents to be prepared by a registered design professional.
Exceptions: The following may be exempt from the requirements above depending on the exact nature of the work, subject to the building official's authority to require additional construction documents to be prepared by a registered design professional where special conditions exist:
1. Tenant improvements, change in use/occupancy, and alterations less than 1,500 square feet and not exceeding two (2) stories in height, involving a B, M, S1, S2, F1, and F2 occupancy classification, excluding F1 occupancies used for the manufacturing of furniture and woodworking facilities, and occupancies storing flammable and/or combustible materials.
2. Minor interior non-structural remodels less than 2,500 square feet involving a B, M, A, S1, S2, F1, F2, I, and R occupancy group.
3. Group R-3 and U occupancies not exceeding three (3) stories in height.
4. Wood pole structures not exceeding 1000 square feet, 10' max. bent spacing and/or a 10' eave height.
5. Group R dwelling units not exceeding two (2) units.
Delete IRC section R109.1.3 and replace with the following:
Floodplain Inspections. For construction in areas prone to flooding as established by table R301.2(1), upon placement of the lowest floor, including basement, the building official is authorized to require submission of documentation of the elevation of the lowest floor, including basement, required in section R322.
IBC section 109.4; IRC section R108.6, "Work Commencing Before Permit Issuance" is amended to read as follows: Any person who commences any work on a building or structure before obtaining the necessary permit, shall be subject to an investigation fee in the amount established by the building official up to quadruple of the permit fee. Investigation fees shall be in addition to the required permit fee.
IBC section 116, "Unsafe Structures And Equipment" is deleted and repealed in its entirety.
IBC section 202, definition for "Agricultural Building," as used within the IBC and as referred to in Idaho Code § 39-4116 (exempting "agricultural buildings" from the requirements of the codes enumerated in Title 39, Chapter 41, of the Idaho Code), shall be amended as follows:
AGRICULTURAL BUILDING: (A) An "Agricultural Building" is a structure that is designed and constructed solely for one or more of the following purposes:
(1) Livestock shelters or buildings, including shade structures and milking barns;
(2) Poultry buildings or shelter;
(3) Barns;
(4) Storage of equipment and machinery used exclusively in agriculture;
(5) Horticultural structures, including detached production greenhouses and crop protection shelters;
(6) Grain silos; and
(7) Stables.
(B) However, notwithstanding the foregoing, no building shall be considered an "agricultural building" if it is:
(1) Used as a place of human habitation; or
(2) Used as a place of employment where agricultural products are processed, treated or packaged; or
(3) Open to use by the public; or
(4) A shop and/or machinery repair building; or
(5) A garage or building used for storage of personal use vehicles and/or vehicles licensed for use on public roads.
(C) "Equipment and machinery used exclusively in agriculture" means farm implements and other equipment and machinery that are used exclusively on land actively devoted to agriculture and are not used on public highways except as necessary for access to land actively devoted to agriculture.
(D) "Land actively devoted to agriculture" means real property meeting the eligibility criteria for appraisal, assessment and taxation as agricultural property as set forth in Idaho Code § 63-604.
IBC section 202, definition for "Registered Design Professional," is amended to read as follows: An individual who is registered or licensed to practice their respective design profession as defined by the statutory requirements of the professional registration laws of the state of Idaho. For purposes of this definition, the term "design profession" shall be limited to the practices of architecture and engineering.
IRC section R202, definition for "Registered Design Professional," is amended to read as follows: An individual who is registered or licensed to practice their respective design profession as defined by the statutory requirements of the professional registration laws of the state of Idaho. For purposes of this definition, the term "design profession" shall be limited to the practices of architecture and engineering.
IRC section R202, definition for "Townhouse" is amended to read as follows: Townhouse is a single family dwelling unit constructed in a row of attached units separated by property lines and with open space on at least 2 sides.
IRC table R301.2(1) is amended to read as follows:
TABLE R301.2(1) CLIMATIC AND GEOGRAPHIC DESIGN CRITERIA
GROUND SNOW LOADo: 20 PSF.
Design roof load shall not be less than a uniform snow load of 25 psf.
WIND DESIGN:
SPEEDd (mph): 115
Wind speed from the basic wind speed map [Figure R301.2(4)A]. Wind exposure category shall be determined in accordance with Section R301.2.1.4 WIND DESIGN
TOPOGRAPHIC EFFECTSk: NO
In accordance with Section R301.2.1.5
SPECIAL WIND REGIONl: NO
WIND-BORNE DEBRIS ZONEm: NO
SEISMIC DESIGN CATEGORYf: B
In accordance with Section R301.2.2.1
SUBJECT TO DAMAGE FROM:
WEATHERINGa: Severe
as determined from the Weathering Probability Map [Figure R301.2(3)]. The grade of masonry units shall be determined from ASTM C34, C55, C62, C73, C90, C129, C145, C216 or C652.
FROST LINE DEPTH b: 24 inches
TERMITEc:
Slight to Moderate Based on history of local subterranean termite damage.
WINTER DESIGN TEMPe: 10 degrees F
The outdoor design dry-bulb temperature shall be selected from the columns of 97½-percent values for winter from Appendix D of the International Plumbing Code or as determined by the Building Official.
ICE BARRIER UNDERLAYMENT REQUIREDh: NO
In accordance with Sections R905.2.7.1, R905.4.3.1, R905.5.3.1, R905.6.3.1, R905.7.3.1 and 21 R905.8.3.1, where there has been a history of local damage from the effects of ice damming.
FLOOD HAZARDSg: Floodplain ordinance effective 4/18/2011, with current revisions and FIRM maps as currently adopted.
AIR FREEZING INDEXi: 860
Based on the 100-year return period air freezing index (BF-days) from Figure R403.3(2) or from the 100-year (99%) value on the National Climatic Data Center data table "Air Freezing Index-USA Method (Base 32° Fahrenheit)" at www.ncdc.noaa.gov/fpsf.html.
MEAN ANNUAL TEMPj: 51.8 degrees F
Based on the mean annual temperature from the National Climatic Data Center data table "Air Freezing Index-USA Method (Base 32°F)" at www.ncdc.noaa.gov/fpsf.html.
MANUAL J DESIGN CRITERIAn:
Elevation: 2838
Latitude: 43.57 deg. N.
Winter heating: 16 deg.
Summer cooling: 93 deg.
Altitude correction factor: .98
Indoor design temperature: 75 deg.
Design temperature cooling: Dry-Bulb 94 deg. / Wet-Bulb 63 deg.
Heating temperature difference: 60 deg.
Cooling temperature difference: 20 deg.
Wind velocity heating: 15.0
Wind velocity cooling: 7.5
Coincident wet bulb: 63 deg.
Daily range: High
Winter humidity: 50%
Summer humidity: 50%
All footnotes published underneath Table R301.2(1) in the code are applicable here and are incorporated herein by this reference.
Delete Section R301.2.1.2 Protection of Openings.
Delete Table R302.1(1) and replace with the following:
TABLE R302.1(1) - EXTERIOR WALLS
Exterior Wall Element | Minimum Fire- Resistance Rating | Minimum Fire Separation Distance |
Exterior Wall Element | Minimum Fire- Resistance Rating | Minimum Fire Separation Distance | |
Walls | Fire-resistance rated | 1 hour-tested in accordance with ASTM E 119 or UL263 with exposure from both sides | < 3 feet |
Not fire- resistance rated | 0 hours | = 3 feet | |
Projections | Fire-resistance rated | 1 hour on the underside | = 2 feet to < 3 feet |
Not fire- resistance rated | 0 hours | = 3 feet | |
Openings in walls | Not allowed | n/a | < 3 feet |
24% maximum of wall area | 0 hours | = 3 feet to < 5 feet | |
Unlimited | 0 hours | 5 feet | |
Penetrations | All | Comply with section R302.4 | < 3 feet |
None required | = 3 feet | ||
For SI: 1 foot = 304.8 mm.
N/A = Not Applicable
a The fire-resistance rating shall be permitted to be reduced to zero (0) hours on the underside of the eave overhang if fireblocking is provided from the wall top plate to the underside of the roof sheathing.
b The fire-resistance rating shall be permitted to be reduced to zero (0) hours on the underside of the rake overhang where gable vent openings are not installed.
IRC section R302.5.1, "Opening Protection" is amended to read as follows: Openings from a private garage directly into a room used for sleeping purposes shall not be permitted. Other openings between the garage and residence shall be equipped with solid wood doors not less than 13/8 inches (35 mm) in thickness, solid or honeycomb core steel doors not less than 13/8 inches (35 mm) thick, or 20-minute fire-rated doors. These doors shall be provided with 2 self-closing hinges or one closing device capable of closing the door to a latching point.
IRC section R302.6, "Dwelling/Garage Fire Separation" is amended to read as follows: The private garage shall be separated from the residence and its attic area by means of minimum 5/8 inch type X gypsum board applied to garage side.
Delete Section R302.13 Fire protection of floors.
Delete IRC section R303.4 and replace with the following: R303.4 Mechanical Ventilation. Dwelling units shall be provided with whole-house mechanical ventilation in accordance with section M1505.4.
IRC section M1507.3.1, System Design. Add the following to the end of the section: Outdoor air shall be ducted predominantly horizontal to avoid chimney effect. Outdoor air ducts will contain an accessible back draft damper and be designed to have an open cross section of twenty (20) square inches per one thousand (1,000) square feet of conditioned space.
Delete the exception contained under IRC section R313.1, "Townhouse Automatic Fire Sprinkler Systems" and replace with the following:
Exception: Automatic residential fire sprinkler systems shall not be required in townhouses where either two (2) one (1)-hour fire-resistance-rated walls or a common two (2)-hour fire-resistance rated wall, as specified in item number 2 of Section R302.2.2 is installed between dwelling units or when additions or alterations are made to existing townhouses that do not have an automatic residential fire sprinkler system installed.
Delete IRC section R313.2. One- and two-family dwellings automatic fire sprinkler systems.
Delete the exceptions under Section R314.2.2 Alterations, repairs and additions, and replace with the following: Exceptions: 1. Work involving the exterior surfaces of dwellings, such as, but not limited to, replacement of roofing or siding, or the addition or replacement of windows or doors, or the addition of a porch or deck or electrical permits, are exempt from the requirements of this section. 2. Installation, alteration or repairs of plumbing or mechanical systems are exempt from the requirements of this section.
Add the following to IRC section R315.2:
Where Required In Existing Dwellings:
Exceptions:
1. Work involving the exterior surfaces of dwellings, such as, but not limited to, replacement of roofing or siding, or the addition or replacement of windows or doors, or the addition of a porch or deck or electrical permits, are exempt from the requirements of this section; and
2. Installation, alteration or repairs of noncombustion plumbing or mechanical systems are exempt from the requirements of this section.
IRC section R315.2, "Carbon Monoxide Alarms Where Required In Existing Dwellings" is amended to read: "Where work requiring a permit occurs in existing dwellings that have attached garages or in existing dwellings within which fuel fired appliances exist, carbon monoxide alarms shall be provided in accordance with section R315.1.
Exceptions:
1. Work involving the exterior surfaces of dwellings, such as, but not limited to, replacement of roofing or siding, or the addition or replacement of windows or doors, or the addition of a porch or deck, or electrical permits, are exempt from the requirements of this section.
2. Installation, alteration or repairs of non-combustion plumbing or mechanical systems are exempt from the requirements of this section.
Delete the exceptions under Section R315.2.2 Alterations, repairs and additions, and replace with the following: Exceptions: 1. Work involving the exterior surfaces of dwellings, such as, but not limited to, replacement of roofing or siding, or the addition or replacement of windows or doors, or the addition of a porch or deck or electrical permits, are exempt from the requirements of this section. 2. Installation, alteration or repairs of noncombustion plumbing or mechanical systems are exempt from the requirements of this section.
Delete IRC section R322.1.10 As-built elevation documentation.
Delete Section R322.2.1 and replace with the following: R322.2.1 Elevation requirements. 1. Buildings and structures in flood hazard areas, including flood hazard areas designated as Coastal A Zones, shall have the lowest floors elevated to or above the base flood elevation. 2. In areas of shallow flooding (AO Zones), buildings and structures shall have the lowest floors (including basement) elevated to a height above the highest adjacent grade of not less than the depth number specified in feet (mm) on the FIRM, or not less than two (2) feet (610 mm) if a depth number is not specified. 3. Basement floors that are below grade on all sides shall be elevated to or above base flood elevation. Exception: Enclosed areas below the design flood elevation, including basements with floors that are not below grade on all sides, shall meet the requirements of Section R322.2.2.
Delete subparagraph 2.1 of Section R322.2.2 Enclosed area below design flood elevation, and replace with the following: 2.1. The total net area of all openings shall be at least one (1) square inch (645 mm2) for each square foot (0.093 m2) of enclosed area, or the opening shall be designed and the construction documents shall include a statement that the design and installation of the openings will provide for equalization of hydrostatic flood forces on exterior walls by allowing the automatic entry and exit of floodwaters.
Delete IRC section R322.2.2 paragraph 2.2, and replace with the following:
The total net area of all openings shall be at least one (1) square inch (645 mm2) for each square foot (0.093 m2) of enclosed area, or the opening shall be designed and the construction documents shall include a statement that the design and installation of the openings will provide for equalization of hydrostatic flood forces on exterior walls by allowing the automatic entry and exit of floodwaters.
IRC section R402.1, "Wood Foundations" is amended to read: Wood foundation systems shall be designed by a licensed architect or engineer, licensed in the state of Idaho, and designed and installed in accordance with the provisions of this code.
Add the following footnote to the title of IECC table 402.1.1:
k. Insulation And Fenestration Requirements By Component: k. For residential log home building thermal envelope construction requirements see section 402.6.
Delete the rows in Table R402.1.2 for climate zones "5 and Marine 4" and "6" and replace with the following:
TABLE R402.1.2 INSULATION AND FENESTRATION REQUIREMENTS BY COMPONENTa | ||||||||||
Climate Zone | Fene strati on U- Factorb | Skylightb
U- factor | Glazed Fene strati on SHG Cb,e |
Ceiling R- Value | Wood Frame Wall R- Value | Mass Wall R- Valuei |
Floor R- Value | Basement c Wall R- Value | Slab d R- Value & Depth | Cra wlsp acec Wall R- Value |
5 | 0.32 | 0.55 | NR | 38 | 20 or 13+ 5h |
13/1 7 | 30g |
15/1 9 | 10, 2 ft | 15/1 9 |
6 | 0.30 | 0.55 | NR | 49 | 22 or 13+ 5h |
15/2 0 | 30g |
15/1 9 | 10, 4 ft | 15/1 9 |
Add the following as footnote k to the title of Table R402.1.2 - Insulation and Fenestration Requirements by Component: k. For residential log home building thermal envelope construction requirements see Section R402.6.
Delete the rows in Table R402.1.4 for climate zones "5 and Marine 4" and "6" and replace with the following:
TABLE R402.1.4 EQUIVALENT U-FACTORSa | ||||||||
Climate Zone | Fenest ration U- factor | Skylight U- factor | Ceiling U- factor | Frame Wall U- factor | Mass Wall U- factorb |
Floor U- factor | Basement Wall U- factor | Crawl space Wall U- factor |
5 | 0.32 | 0.55 | 0.030 | 0.060 | 0.082 | 0.033 | 0.050 | 0.055 |
6 | 0.30 | 0.55 | 0.026 | 0.057 | 0.060 | 0.033 | 0.050 | 0.055 |
Delete Section R402.4.1 and replace with the following: R402.4.1 Building thermal envelope. 1. Until June 30, 2021, the building thermal envelope shall comply with Sections R402.4.1.1 (Installation) and either Section R402.4.1.2 (Testing) or Section R402.4.1.3 (Visual inspection). 2. Effective July 1, 2021, the building thermal envelope of a minimum of twenty percent (20%) of all new single-family homes constructed by each builder shall comply with Section R402.4.1.1 (Installation) and Section R402.4.1.2 (Testing). The authority having jurisdiction may: 2.1. Determine how to enforce this requirement, starting with the fifth house and continuing with each subsequent fifth house. 2.2. Waive this requirement if significant testing indicates the five (5) air changes per hour (ACH) requirement is consistently being met or exceeded (resulting in a lower ACH). 2.3. Grant exceptions to this requirement in rural areas where testing equipment is not available or cost effective. 3. Effective July 1, 2021, the building thermal envelope of eighty percent (80%) of all new single-family homes constructed by each builder shall comply with Section R402.4.1.1 (Installation) and either Section R402.4.1.2 (Testing) or Section R402.4.1.3 (Visual inspection). 4. The sealing methods between dissimilar materials shall allow for differential expansion and contraction.
Delete Section R402.4.1.1 and replace with the following: R402.4.1.1 Installation. The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance with the manufacturer's instructions and the criteria listed in Table R402.4.1.1, as applicable to the method of construction.
Delete Section R402.4.1.2 and replace with the following: R402.4.1.2 Testing. Testing building envelope tightness and insulation installation shall be considered acceptable when tested air leakage is less than five (5) air changes per hour (ACH) when tested with a blower door at a pressure of 33.5 psf (50 Pa). Testing shall occur after rough in and after installation of penetrations of the building envelope, including penetrations for utilities, plumbing, electrical, ventilation and combustion appliances. Testing shall be conducted in accordance with RESNET/ ICC 380, ASTM E 779 or ASTM E 1827 and reported at a pressure of 0.2-inch w.g. (50 Pascals). During testing: 1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed. 2. Dampers shall be closed, but not sealed, including exhaust, intake, makeup air, backdraft and flue dampers. 3. Interior doors shall be open. 4. Exterior openings for continuous ventilation systems and heat recovery ventilators shall be closed and sealed. 5. Heating and cooling system(s) shall be turned off. 6. HVAC ducts shall not be sealed. 7. Supply and return registers shall not be sealed.
Add the following as Section R402.4.1.3: R402.4.1.3 Visual inspection. Building envelope tightness and insulation installation shall be considered acceptable when the items listed in Table R402.4.1.1, applicable to the method of construction, are field verified. Where required by code official an approved party independent from the installer of the insulation shall inspect the air barrier and insulation.
Delete section IECC 402.4.3 and replace with the following:
Fireplaces. New wood-burning fireplaces shall have tight-fitting flue dampers and outdoor combustion air.
Add the following as Section R402.6: R402.6 Residential log home thermal envelope. Residential log home construction shall comply with Section R401 (General), Section R402.4 (Air leakage), Section R402.5 (Maximum fenestration U-factor and SHGC), Section R403.1 (Controls), the mandatory sections of Sections R403.3 through R403.9, Section R404 (Electrical Power and Lighting Systems), and either 1., 2., or 3. as follows: 1. Sections R402.2 through R402.3, Section R403.3.1 (Insulation), Section R404.1 (Lightning equipment), and Table R402.6 (Log Home Prescriptive Thermal Envelope Requirements by Component). 2. Section R405 (Simulated Performance Alternative). 3. REScheck (U.S. Department of Energy Building Codes Program).
Add the following as Table R402.6:
TABLE 402.6 LOG HOME PRESCRIPTIVE THERMAL ENVELOPE REQUIREMENTS BY COMPONENT
For SI: 1 foot = 304.8 mm.
Climate Zone | Fenestration U-Factora | Skylight U-Factor | Glazed Fenestration SHGC | Ceiling R-Value | Min. Average Log Size In Inches | Floor R-Value | Basement Wall R-Valued | Slab R-Value & Depthb | Crawl Space Wall R-Valued |
5, 6 - High efficiency equipment pathc | 0.32 | 0.60 | NR | 49 | 5 | 30 | 15/19 | 10.4 ft. | 10/13 |
5 | 0.32 | 0.60 | NR | 49 | 8 | 30 | 10/13 | 10.2 ft. | 10/13 |
6 | 0.30 | 0.60 | NR | 49 | 8 | 30 | 15/19 | 10.4 ft. | 10/13 |
a. The fenestration U-factor column excludes skylights. The SHGC column applies to all glazed fenestration.
b. R-5 shall be added to the required slab edge R-values for heated slabs.
c. 90% AFUE natural gas or propane, 84% AFUE oil, or 15 SEER heat pump heating equipment (zonal electric resistance heating equipment such as electric base board electric resistance heating equipment as the sole source for heating is considered compliant with the high efficiency equipment path).
d. "15/19" means R-15 continuous insulated sheathing on the interior or exterior of the home or R-19 cavity insulation at the interior of the basement wall. "15/19" shall be permitted to be met with R-13 cavity insulation on the interior of the basement wall plus R-5 continuous insulated sheathing on the interior or exterior of the home. "10/13" means R-10 continuous insulated sheathing on the interior or exterior of the home or R-13 cavity insulation at the interior of the basement wall.
Delete Section R403.5.3 and replace with the following: R403.5.3 Hot water pipe insulation (Prescriptive). Insulation for hot water piping with a thermal resistance, R-value, of not less than R-3 shall be applied to the following: 1. Piping serving more than one (1) dwelling unit. 2. Piping located outside the conditioned space. 3. Piping located under a floor slab. 4. Buried piping. 5. Supply and return piping in recirculation systems other than demand recirculation systems.
Delete Tables R403.4 Minimum Depth (D) and Width (W) of Crushed Stone Footings (inches), R403.1(1) Minimum Width and Thickness for Concrete Footings for Light-Frame Construction (inches), R403.1(2) Minimum Width and Thickness for Concrete Footings for Light-Frame Construction and Brick Veneer (inches), and R403.1(3) Minimum Width and Thickness for Concrete Footings with Cast-In-Place or Fully Grouted Masonry Wall Construction (inches).
Add the following as Table R403.1:
TABLE R403.1
MINIMUM WIDTH OF CONCRETE, PRECAST, OR MASONRY FOOTINGS (inches)a
LOAD-BEARING VALUE OF SOIL (psf) | ||||
1,500 | 2,000 | 3,000 | > 4,000 |
LOAD-BEARING VALUE OF SOIL (psf) | ||||
1,500 | 2,000 | 3,000 | > 4,000 | |
Conventional light-frame construction | ||||
1-story | 12 | 12 | 12 | 12 |
2-story | 15 | 12 | 12 | 12 |
3-story | 23 | 17 | 12 | 12 |
4-inch brick veneer over light frame or 8-inch hollow concrete masonry | ||||
1-story | 12 | 12 | 12 | 12 |
2-story | 21 | 16 | 12 | 12 |
3-story | 32 | 24 | 16 | 12 |
8-inch solid or fully grouted masonry | ||||
1-story | 16 | 12 | 12 | 12 |
2-story | 29 | 21 | 14 | 12 |
3-story | 42 | 32 | 21 | 16 |
For SI: 1 inch = 25.4 mm, 1 pound per square foot = 0.0479 kPa.
a Where minimum footing width is twelve (12) inches, use of a single wythe of solid or fully grouted twelve (12)-inch nominal concrete masonry units is permitted.
Delete Section R403.1.1 and replace with the following: R403.1.1 Minimum size. Minimum sizes for concrete and masonry footings shall be as set forth in Table R403.1 and Figure R403.1(1). The footing width (W) shall be based on the load bearing value of the soil in accordance with Table R401.4.1. Spread footings shall be at least six (6) inches in thickness (T). Footing projections (P) shall be at least two (2) inches and shall not exceed the thickness of the footing. The size of footings supporting piers and columns shall be based on the tributary load and allowable soil pressure in accordance with Table R401.4.1. Footings for wood foundations shall be in accordance with the details set forth in Section R403.2 and Figures R403.1(2) and R403.1(3).
Delete Section R404.1 and replace with the following: R404.1 Lighting equipment (Mandatory). A minimum of seventy-five percent (75%) of the lamps in permanently installed lighting fixtures shall be high-efficacy lamps or a minimum of seventy-five percent (75%) of the permanently installed lighting fixtures shall contain only high efficacy lamps.
Delete Section R406.3 and replace with the following: R406.3 Energy Rating Index. The Energy Rating Index (ERI) shall be determined in accordance with RESNET/ICC 301. Energy used to recharge or refuel a vehicle used for transportation on roads that are not on the building site shall not be included in the ERI reference design or the rated design.
Delete Table R406.4 and replace with the following:
Table R406.4 - Maximum Energy Rating Index
Climate Zone | Energy Rating Indexa |
5 | 68 |
6 | 68 |
a Where on-site renewable energy is included for compliance using the ERI analysis of Section R406.4, the building shall meet the mandatory requirements of Section R406.2, and the building thermal envelope shall be greater than or equal to the levels of efficiency and SHGC in Table R402.1.2 or Table R402.1.4 of the 2015 International Energy Conservation Code.
Delete Section R602.10 and replace with the following: R602.10 Wall bracing. Buildings shall be braced in accordance with this Section or, when applicable Section R602.12, or the most current edition of APA System Report SR-102 as an alternate method. Where a building, or portion thereof, does not comply with one (1) or more of the bracing requirements in this Section, those portions shall be designed and constructed in accordance with Section R301.1.
References To Other Codes. Where any provisions of the codes that are adopted in this section make reference to other construction and safety-related model codes or standards which have not been adopted by the city of Caldwell, to the extent possible, such reference should be construed as pertaining to the equivalent code or standard that has been duly adopted by the city of Caldwell.
Delete IRC section N1102.4.3 and replace with the following:
Fireplaces. New wood-burning fireplaces shall have tight-fitting flue dampers and outdoor combustion air.
IBC table 2902.1, "Footnote F" is amended to read: "f. Drinking fountains are not required for an occupant load of thirty (30) or fewer."
IBC table 2902.1, "Footnote G" is amended to read: "g. For business occupancies, excluding restaurants, and mercantile occupancies with an occupant load of thirty (30) or fewer, service sinks shall not be required."
Add the following as Section C101.5.2: C101.5.2 Industrial, electronic, and manufacturing equipment. Buildings or portions thereof that are heated or cooled exclusively to maintain the required operating temperature of industrial, electronic, or manufacturing equipment shall be exempt from the provisions of this code. Such buildings or portions thereof shall be separated from connected conditioned space by building thermal envelope assemblies complying with this code.
Add the following as an exception under Section C402.5 Air leakage– thermal envelope (Mandatory): Exception: For buildings having over fifty thousand (50,000) square feet of conditioned floor area, air leakage testing shall be permitted to be conducted on less than the whole building, provided the following portions of the building are tested and their measured air leakage is area-weighted by the surface areas of the building envelope: 1. The entire floor area of all stories that have any spaces directly under a roof. 2.The entire floor area of all stories that have a building entrance or loading dock. 3. Representative above-grade wall sections of the building totaling at least twenty-five percent (25%) of the above-grade wall area enclosing the remaining conditioned space. Floor area tested under subparagraphs 1. or 2. of this exception shall not be included in the twenty-five percent (25%) of above grade wall sections tested under this subparagraph.
Add the following as exception number 7 under Section C403.5 Economizers (Prescriptive): 7.Unusual outdoor air contaminate conditions - Systems where special outside air filtration and treatment for the reduction and treatment of unusual outdoor contaminants, makes an air economizer infeasible.
Delete Table C404.5.1 and replace with the following:
TABLES C404.5.1 PIPING VOLUME AND MAXIMUM PIPING LENGTHS | |||
NORMAL PIPE SIZE (inches) | VOLUME (Liquid ounces per foot length) | MAXIMUM PIPING LENGTH | |
Public lavatory faucets | Other fixtures and appliances | ||
1/4 | 0.33 | 31 | 50 |
5/16 | 0.5 | N/A - non-standard size | 50 |
3/8 | 0.75 | 17 | 50 |
1/2 | 1.5 | 10 | 43 |
TABLES C404.5.1 PIPING VOLUME AND MAXIMUM PIPING LENGTHS | |||
NORMAL PIPE SIZE (inches) | VOLUME (Liquid ounces per foot length) | MAXIMUM PIPING LENGTH | |
Public lavatory faucets | Other fixtures and appliances |
TABLES C404.5.1 PIPING VOLUME AND MAXIMUM PIPING LENGTHS | |||
NORMAL PIPE SIZE (inches) | VOLUME (Liquid ounces per foot length) | MAXIMUM PIPING LENGTH | |
Public lavatory faucets | Other fixtures and appliances | ||
5/8 | 2 | 7 | 32 |
3/4 | 3 | 5 | 21 |
7/8 | 4 | N/A - non-standard size | 16 |
1 | 5 | 3 | 13 |
1 1/4 | 8 | 2 | 8 |
1 1/2 | 11 | 1 | 6 |
2 or larger | 18 | 1 | 4 |
For SI: 1 inch = 25.4 mm; 1 foot = 304.8 mm; 1 liquid ounce = 0.030 L; 1 gallon = 128 ounces.
(Ord. 2852, 12-20-2010; Ord. 2951, 11-18-2013, eff. 1-1-2014; Ord. 3021, 11-16-2015, eff. 1-1-2016; Ord. 3044, 3-7-2016; Ord. 3127, 12-18-2017; Ord. 3305, 12-21-2020)