1505.05 STORAGE TANKS: UNDER 125 GALLONS.
   All owners or tenants of residential premises units equipped with storage tanks or cylinders with holding capacity of less than 125 water gallons of liquefied petroleum (LP) gas, shall be subject to the following rules and regulations.
   (a)   All such storage tanks or cylinders shall be of a type approved by the Federal Department of Transportation;
   (b)   All such storage tanks or cylinders shall be installed upon a concrete slab of not less than four inches in thickness extending not less than six inches at every point beyond all sides of the tank or cylinder wall;
   (c)   All such storage tanks or cylinders shall be anchored by at least a one-inch steel chain, cable or comparable fasteners;
   (d)   No such storage tank or cylinder shall ever be installed underground, nor shall any such storage tank or cylinder ever be installed upon any roof or other location determined by the Fire Prevention Bureau to be hazardous or unsuitable in any way. (Ord. 26-78. Passed 5-2-78.)