(A) On premises of large ground area, one yard hydrant shall be provided for each 20,000 square feet of ground area, and such hydrants shall be spaced not more than 300 feet apart.
(B) Yard hydrants in lumber yards shall be spaced not more than 250 feet apart and shall be in such number and so located that streams therefrom, when used in first-aid or Fire Department firefighting, reach all areas on the premises, including those within lumber sheds.
(C) Every required yard hydrant within a lumber yard shall be equipped with attached hose kept within a hose house.
(Ord. 34-74, passed 3-18-1974; Ord. 28-06, passed 3-6-2006)