§ 16.04.120 APPENDIX B FIRE-FLOW REQUIREMENTS FOR BUILDINGS AMENDMENTS.
   TABLE B105.2
   REQUIRED FIRE-FLOW FOR BUILDINGS OTHER THAN ONE-AND TWO-FAMILY
   DWELLINGS, GROUP R-3 AND R-4 BUILDINGS AND TOWNHOUSES
 
AUTOMATIC SPRINKLER SYSTEM (Design Standard)
MINIMUM FIRE-FLOW (gallons per minute)
FLOW DURATION (hours)
No automatic sprinkler system
Value in Table B105.1(2)
Duration in Table B105.1(2)
Section 903.3.1.1 or Section 903.3.1.2 of the California Fire Code
50% of the value in Table B105.1(2) but not less than 1500
Duration in Table B105.1(2)
For SI: 1 square foot = 0.0929 m2, 1 gallon per minute = 3.785 L/m
 