TABLE B105.2
REQUIRED FIRE-FLOW FOR BUILDINGS OTHER THAN ONE-AND TWO-FAMILY
DWELLINGS, GROUP R-3 AND R-4 BUILDINGS AND TOWNHOUSES
AUTOMATIC SPRINKLER SYSTEM (Design Standard) | MINIMUM FIRE-FLOW (gallons per minute) | FLOW DURATION (hours) |
No automatic sprinkler system | Value in Table B105.1(2) | Duration in Table B105.1(2) |
Section 903.3.1.1 or Section 903.3.1.2 of the California Fire Code | 50% of the value in Table B105.1(2) but not less than 1500 | Duration in Table B105.1(2) |
For SI: 1 square foot = 0.0929 m2, 1 gallon per minute = 3.785 L/m |