§ 6.07 FLAMMABLE AND COMBUSTIBLE LIQUIDS AND GASES PLAN REVIEW.
   Before construction at any location or commencement of any operation that includes the installation of any tank or container, as outlined in this section, a plan review application must be submitted, along with the plan review fee as set forth in City Code Appendix A. Plans submitted for review must include all associated dispensers and piping. The application must include a complete set of plans and all supporting documentation required pursuant to the MSFC. Plan review by the City Fire Prevention Division shall be required for the following installations:
   (a)   Permanent installation of any above-ground or underground tank containing flammable or combustible liquids;
   (b)   Temporary installation of any above-ground tank containing 60 gallons or more of flammable or combustible liquids;
   (c)   Permanent installation of any underground container of liquefied petroleum (LP) gas;
   (d)   Permanent installation of any above-ground container of liquefied petroleum (LP) gas with a liquid capacity of over 499 gallons or where the aggregate liquid capacity of all above-ground containers for the site exceeds 2,000 gallons; and
   (e)   Temporary installation of any above-ground container of liquefied petroleum (LP) gas with a liquid capacity exceeding 60 gallons.