8-1-5: ADOPTION OF THE INTERNATIONAL MECHANICAL CODE WITH STATE AMENDMENTS:
International Mechanical Code. The 2018 Edition, including appendix “A,” (herein IMC) is adopted and incorporated by reference with the following amendments: (3-20-20)T
   A.   Where differences occur between the IMC and Title 54, Chapter 50, Idaho Code and IDAPA 07, Title 07, the provisions in Idaho Code and IDAPA rules apply. (3-20-20)T
   B.   All references to the International Plumbing Code (IPC) are construed as referring to the Idaho State Plumbing Code (ISPC) as adopted and amended by the Idaho State Plumbing Board. (3-20-20)T
   C.   All references to the International Code Council Electrical Code (ICC EC) are construed as referring to the National Electrical Code (NEC) as adopted and amended by the Idaho State Electrical Board. (3-20-20)T
   D.   Section 109. Delete. (3-20-20)T
   E.   Section 202 Definitions. Delete the definitions provided in the code for the terms identified herein this paragraph and replace with the following: (3-20-20)T
      i.   Light-Duty Cooking Appliance. Light-duty cooking appliances include gas and electric ovens(including standard, bake, roasting, revolving, retherm, convection, combination convection/steamer, countertop conveyorized baking/finishing, deck, pastry, and electric and gas conveyor pizza ovens), electric and gas steamjacketed kettles, electric and gas pasta cookers, electric and gas compartment steamers (both pressure and atmospheric) and electric and gas cheesemelters.(3-20-20)T
      ii.   Medium-Duty Cooking Appliance. Medium-duty cooking appliances include electric discrete element ranges (with or without oven), electric and gas hot-top ranges, electric and gas griddles, electric and gas double sided griddles, electric and gas fryers (including open deep fat fryers, donut fryers, kettle fryers and pressure fryers), electric and gas tilting skillets (braising pans) and electric and gas rotisseries.(3-20-20)T
   F.   Section 401.1 Scope. Add the following: Exception: The principles specified in ASHREA 62-2010may be used as an alternative to this chapter to demonstrate compliance with required ventilation air for occupants.(3-20-20)T
   G.   Section 504.8.1 Material and size. Add the following exception: Dryer duct may be constructed of 0.013 (30 gauge) or equivalent if prefabricated 0.016 (28 gauge) ducts and fittings are not available. (3-20-20)T
   H.   Table 603.4 Duct Construction Minimum Sheet Metal Thickness for Single Dwelling Units. Add the following exception to the Table: Round duct, enclosed rectangular ducts and fittings less than fourteen (14) inches may be constructed of 0.013 (30 gauge) or equivalent if prefabricated 0.016 (28 gauge) ducts and fittings are not available. (2020-10, 12-23-2020)