Provided, in addition to the requirements of § 152.061, that:
(A) They are driven or drilled wells located on ground higher than surrounding ground to assure positive drainage from the well;
(B) They require no other structures (e.g., a well house);
(C) Well casings are water tight to a distance of at least 25 feet below the ground surface and the well casing height is a minimum of two feet above the base flood elevation or capped with a watertight seal and vented two feet above the base flood elevation;
(D) Water supply lines have a watertight seal where the lines enter the casing;
(E) All pumps and electrical lines and equipment are either of the submersible type or are adequately flood proofed; and
(F) Check valves are installed on main water lines at wells and at all building entry locations.
(Ord. 484, passed 4-20-2015)
Statutory reference:
Related provisions, see ARM § 36.15.602(6) and 44 C.F.R. § 60.3(a)(5)