§ 94.074 REQUIRED WATER SUPPLY FOR FIRE PROTECTION.
   (A)   All Class 1 structures or portions of Class 1 structures hereafter constructed shall be provided with a water supply capable of providing the required fire flow, for fire-fighting purposes for a minimum period of two hours. The water supply shall be from a source as set forth in section 903.2 of 675 IAC 22-2.2.
   (B)   In setting the requirements for fire flow, the Beech Grove Fire Department shall use 675 IAC 22-2.2, Appendix III-A as a guide. Notwithstanding the provisions of this subsection, a reduction in required fire flow of 75% is allowed when the building is providing with an approved automatic sprinkler system. The resulting fire flow shall not be less than 1,000 gpm at 20 psi residual.
(Ord. 1-2003, passed 5-5-03)