The following shall regulate fire protection measures:
(A) Fire hydrants with control valves meeting the requirements of the village shall be provided in all subdivisions.
(B) Fire hydrants shall be spaced at a maximum of 400 feet apart.
(C) Fire hydrants shall be installed at all street intersections, at the ends of cul-de-sacs, and at the ends of dead-end water mains. Hydrants should be located near property lines where practical.
(D) The minimum size of a water main serving any fire hydrant shall not be less than eight inches in diameter.
(Ord. 2024-16, passed 2-19-2024)