§ 51.22 REQUIRED EQUIPMENT.
   (A)   There shall be installed in every connection to the city water system one stop and waste valve which shall be installed at a point between the curb stop and the meter so that the water may be turned off and the meter and house plumbing entirely drained. There shall be installed another stop and waste cock and check valve in the pipe on the house side of the meter.
   (B)   There shall be installed a meter yoke or couplings of the type approved by the city for convenient installation or removal of the meter. All service pipes connected to the city system shall be TYPE K copper, a minimum one-inch inside diameter or its approved equal and in the right-of-way shall be laid at a depth not less than eight feet below the established grade, or as low as the street mains.
(‘81 Code, § 21-10) (Ord. 152, passed 11-13-74; Am. Ord. 835, passed 2-28-08)