10-4-5: WATER SERVICE:
   A.   Connection To Village System Required; Pressure Requirements: The subdivider shall connect with a water main of the Angel Fire municipal water system and provide a water system with service lines to each lot in the subdivision. All lines in the system shall be designed to carry adequate flows for firefighting as specified by the New Mexico state fire marshal: twenty (20) psi and one thousand (1,000) gallons per minute. In no case shall there be a pressure zone exceeding one hundred fifty (150) psi.
   B.   Specifications:
      1.   The minimum line size for looped lines shall be six inches (6"); for nonlooped lines, the minimum line size shall be eight inches (8"). All nonlooped lines shall have a five and one-fourth inch (51/4") fitting with a bleeder valve at the end. All water lines shall be buried a minimum of six feet (6') below the finished grade.
      2.   All service lines shall be of approved materials and sizes.
      3.   All pipe and pipe fittings, accessories, etc., shall be AWWA standards. (Ord. 2002-03, 2-2002)
   C.   Water Hookup Agreement: (Rep. by Ord. 2013-07, 8-13-2013)
   D.   Extensions: Extensions from the existing system to the subdivision shall have additional capacity to serve adjacent properties and for future expansion, as recommended by the village engineer.
   E.   Hydrants: Fire hydrants shall be located within public rights of way, spaced a maximum distance of four hundred feet (400') apart and shall conform to the village fire code 1
   F.   Inspections: Prior to backfilling any water line ditch section, the village shall inspect all pipe, valves, connections and grades, and approve backfill material and procedures. (Ord. 2002-03, 2-2002)

 

Notes

1
1. See title 8, chapter 2 of this code.1.