C = Numerical coefficient as specified in UBC Section 2312(d)
Cp = Numerical coefficient as specified in UBC Section 2312(g) and as set forth in Table No. 23-J
D = The dimension of the structure, in feet, in a direction parallel to the applied forces
f'c = Specified compressive strength of concrete, psi
Fp = Lateral forces on a part of the structure and in the direction under consideration
ft = Allowable tensile stress, psi
hn = Height in feet above the base to level n
I = Occupancy Importance Factor as set forth in Table No. 23-K of the UBC
S = Numerical coefficient for site-structure resonance
V = The total lateral force or shear at the base
W = The total dead load as defined in UBC Section 2302 including the partition loading specified in UBC Section 2304(d) where applicable
Wp = The weight of a portion of a structure or nonstructural component
Z = Numerical coefficient dependent upon the zone as determined by Figure No. 1, of Chapter 23 of the UBC. All areas in California are classified in Zones 3 or 4. For locations in Zone No. 3, Z = 3/4. For locations in Zone No. 4, Z = 1
TABLE NO. 15.07-A RATING CLASSIFICATIONS | |
TYPE OF BUILDING | CLASSIFICATION |
Essential Building | I |
High Risk Building | II |
Medium Risk Building | III |
Low Risk Building | IV |
TABLE NO. 15.07-B TIME LIMITS FOR COMPLIANCE* | |||
REQUIRED ACTION BY OWNER | OBTAIN BUILDING PERMIT WITHIN | COMMENCE CONSTRUCTION WITHIN** | COMPLETE CONSTRUCTION WITHIN |
Complete Structural Alterations or Building Demolition | 1 year | 180 days | 3 years |
Wall Anchor Installation | 180 days | 270 days | 1 year |
* Where two or more buildings under separate ownership are to be rehabilitated simultaneously, an extension of any time limit may be granted by the Building Official based on the average time requirements for the buildings involved, with a suggested minimum extension of 6 months. Such an extension shall be conditioned on submission of a binding rehabilitation agreement between the owners involved, with the actual date of compliance to be determined by the Building Official.
** Measured from the date of building permit issuance. All the other time limits are measured from the date of the order.
TABLE NO. 15.07-C SERVICE PRIORITIES AND EXTENDED TIME PROVISIONS | |||
Rating Classification | Occupant Load | Extension of Time if Wall Anchors are Installed | Minimum Time Periods for Service of Order |
TABLE NO. 15.07-C SERVICE PRIORITIES AND EXTENDED TIME PROVISIONS | |||
Rating Classification | Occupant Load | Extension of Time if Wall Anchors are Installed | Minimum Time Periods for Service of Order |
I (Highest Priority) | Any | 1 year | 0 |
II | 100 or more | 3 years | 90 days |
100 or more | 5 years | 1 year | |
III | 51 to and including 99 | 6 years | 2 years |
20 to and including 50 | 6 years | 3 years | |
IV (Lowest Priority) | Less than 20 | 7 years | 4 years |
TABLE NO. 15.07-D HORIZONTAL FORCE FACTORS BASED ON RATING CLASSIFICATION | |
RATING CLASSIFICATION | IKCS |
I | 0.186 |
II | 0.133 |
III & IV | 0.100 |
TABLE NO. 15.07-E HORIZONTAL FORCE FACTORS "IS" FOR PARTS OR PORTIONS OF STRUCTURES | |
RATING CLASSIFICATION | IS |
I | 1.50 |
II | 1.00 |
III & IV | 0.75 |
TABLE NO. 15.07-F HORIZONTAL FORCE FACTOR "Cp" FOR PARTS OR PORTIONS OF BUILDINGS OR OTHER STRUCTURES1 | ||
Part or Portion of Buildings | Direction of Force | Value of Cp |
TABLE NO. 15.07-F HORIZONTAL FORCE FACTOR "Cp" FOR PARTS OR PORTIONS OF BUILDINGS OR OTHER STRUCTURES1 | ||
Part or Portion of Buildings | Direction of Force | Value of Cp |
Exterior bearing and non-bearing walls, interior bearing walls and partitions, interior non-bearing walls and partitions over ten feet in height, masonry fences over six feet in height. | Normal to Flat Surface
| 0.20
|
Cantilever parapet and other cantilever walls, except retaining walls. | Normal to Flat Surface
| 1.00
|
Exterior and interior ornamentations and appendages
| Any Direction
| 1.00
|
When connected to or a part of a building; towers, tanks, towers and tanks plus contents, racks over 8 feet 3 inches in height plus contents, chimneys, smokestacks, and penthouses. | Any Direction
| 0.202,4 |
When connected to or part of a building: Rigid and rigidly mounted equipment and machinery not required for continued operation of essential occupancies.5 | Any Horizontal Direction | 0.203 |
Tanks plus effective contents resting on the ground.
| Any Direction
| 0.12
|
Floors and roofs acting as diaphragms. | In the plane of the diaphragm
| 0.126 |
Prefabricated structural elements, other than walls, with force applied at center of gravity of assembly. | Any Horizontal Direction
| 0.30
|
Connections for exterior panels or elements.
| Any Direction
| 2.00
|
1. See Subsection 15.07.070.020 for use of Cp.
2. When located in the upper portion of any building with a hn/D ratio of 5 to 1 or greater, the value shall be increased by 50%.
3. For flexible and flexibly mounted equipment and machinery, the appropriate values for Cp shall be determined with consideration given to both the dynamic properties of the equipment and machinery and to the building or structure in which it is placed.
4. The Wp for storage racks shall be the weight of the racks plus contents. The value of Cp for racks over two storage support levels in height shall be 0.16 for the levels below the top two levels.
5. The design of the equipment and machinery and their anchorage is an integral part of the design and specification of such equipment and machinery. The structure to which the equipment or machinery is mounted shall be capable of resisting the anchorage forces (see also UBC Section 2312(k).
6. Floor and roofs acting as diaphragms shall be designed for a minimum force resulting from a Cp of .12 applied to Wp unless a greater force results from the distribution of lateral forces in accordance with UBC Section 2312(e).
TABLE NO. 15.07-G ALLOWABLE VALUE OF HEIGHT-THICKNESS RATIO OF UNREINFORCED MASONRY WALLS WITH A MINIMUM QUALITY MORTAR.1, 2 | ||
BUILDING WITH CROSSWALLS AS DEFINED BY SECTION 15.07.030 | ALL OTHER BUILDINGS | |
Walls of One Story Buildings | 16 | 13 |
First Wall of Multi-Story Buildings | 16 | 15 |
Walls in Top Story of Multi-Story Buildings | 14 | 9 |
All Other Walls | 16 | 13 |
1. Minimum quality mortar shall be determined by laboratory testing in accordance with Section 15.07.080.050.
2. Table 15.07-G is not applicable to buildings of rating classification I. Walls of buildings within rating classification I shall be analyzed in accordance with Subsection 15.07.070.060.
TABLE NO. 15.07-H VALUES FOR EXISTING MATERIALS | |
EXISTING MATERIALS OR CONFIGURATION OF MATERIALS1 | ALLOWABLE VALUES |
TABLE NO. 15.07-H VALUES FOR EXISTING MATERIALS | |
EXISTING MATERIALS OR CONFIGURATION OF MATERIALS1 | ALLOWABLE VALUES |
1. HORIZONTAL DIAPHRAGMS | |
a. Roofs with straight sheathing and roofing applied directly to the sheathing. | 100 lbs. per foot for seismic shear. |
b. Roofs with diagonal sheathing and roofing applied directly to the sheathing. | 400 lbs. per foot for seismic shear. |
c. Floors with straight tongue and groove sheathing. | 150 lbs. per foot for seismic shear. |
d. Floors with straight sheathing and finished wood flooring. | 300 lbs. per foot for seismic shear. |
e. Floors with diagonal sheathing and finished wood flooring. | 450 lbs. per foot for seismic shear. |
f. Floors or roofs with straight sheathing and plaster applied to the joist or rafters.2 | Add 50 lbs. per foot to the allowable values for Items 1a and 1c. |
2. SHEAR WALLS | |
Wood stud walls with lath and plaster. | 100 lbs. per foot each side for seismic
shear. |
3. PLAIN CONCRETE FOOTINGS | f 'c = 1500 psi unless otherwise shown by tests. |
4. DOUGLAS FIR WOOD | Allowable stress same as No. 1 D.F.3 |
5. REINFORCING STEEL | ft = 18,000 lbs. per square inch maximum.3 |
6. STRUCTURAL STEEL | ft = 20,000 lbs. per square inch maximum.3 |
NOTES:
1. Material must be sound and in good condition.
2. The wood lath and plaster must be reattached to existing joints or rafters in a manner approved by the Department.
3. Stresses given may be increased for combinations of loads as specified in Subsection 15.07.070.070(b).
TABLE NO. 15.07-I ALLOWABLE VALUES OF NEW MATERIALS USED IN CONJUNCTION WITH EXISTING CONSTRUCTION1 | |
NEW MATERIALS OR CONFIGURATION OF MATERIALS | ALLOWABLE VALUES |
TABLE NO. 15.07-I ALLOWABLE VALUES OF NEW MATERIALS USED IN CONJUNCTION WITH EXISTING CONSTRUCTION1 | |
NEW MATERIALS OR CONFIGURATION OF MATERIALS | ALLOWABLE VALUES |
1. HORIZONTAL DIAPHRAGMS | |
Plywood sheathing applied directly over existing straight sheathing with ends of plywood sheets bearing on joists or rafters and edges of plywood located on center of individual sheathing boards. | Same as specified in Table No. 25-J for blocked diaphragms.* |
2. SHEAR WALLS | |
a. Plywood sheathing applied directly over existing wood studs. No value shall be given to plywood applied over existing plaster or wood sheathing. | Same as values specified in Table No. 25-K for shear walls. |
b. Dry wall or plaster applied directly over existing wood studs. | 75 percent of the values specified in Table No. 47-I. |
c. Dry wall or plaster applied to plywood sheathing over existing wood studs. | 33-1/3 percent of the values specified in Table No. 47-I. |
3. SHEAR BOLTS | |
Shear bolts and shear dowels embedded a minimum of 8 inches into unreinforced masonry walls. Bolt centered on a 2-1/2 inch diameter hole with a dry-pack or non-shrink grout around circumference of bolt or dowel.1 | 100 percent of the values for solid masonry specified in Table No. 24E. No values larger than those given for 3/4 inch bolts shall be used. |
4. TENSION BOLTS | |
Tension bolts and tension dowels extending through unreinforced masonry walls secured with bearing plates on far side of wall with at least 30 sq. inches of area.2 | 1200 lbs. per bolt or dowel. |
5. WALL ANCHORS (15.07.090.020(a)) | |
Bolts extending to the exterior face of the wall with a 2-1/2 inch round plate under the head. Installed as specified for shear bolts. Spaced not closer than 12 inches on centers.1, 2 | 600 lbs. per bolt. |
6. Bolts or dowels extending to the exterior face of the wall with a 2-1/2 inch round plate under the head and drill at an angle of 22-1/2 degrees to the horizontal. Installed as specified for shear bolts.1, 2 | 1200 lbs. per bolt or dowel. |
* All tables that do not carry a 15.07 number are found in the UBC. | |
7. INFILLED WALLS | |
Reinforced masonry infilled openings in existing unreinforced masonry walls with keys or dowels to match reinforcing. | Same as values specified for unreinforced masonry walls. |
8. REINFORCED MASONRY | |
Masonry piers and walls reinforced per UBC Section 2407. | Same as values specified in UBC Division 26. |
9. REINFORCED CONCRETE | |
Concrete footings, walls and piers reinforced as specified in UBC Division 26 and designed for tributary loads. | Same value as specified in Division 26, UBC. |
10. EXISTING FOUNDATION LOADS | |
Foundation loads for structures exhibiting no evidence of settlement. | Calculated existing foundation loads due to maximum dead load plus live load may be increased 25% for dead load, and may be increased 50% for dead load plus seismic load required by this UBC Division 26. |
NOTES: 1. Bolts and dowels to be tested as specified in Subsection 15.07.080.060.
2. Bolts and dowels to be 1/2 inch minimum in diameter.
TABLE NO. 15.07-J ALLOWABLE SHEAR STRESS FOR TESTED UNREINFORCED MASONRY WALLS | ||
Eighty percent of test results in psi not less than | Average test results of cores in psi | Seismic in-plane shear based on gross area1 |
30 plus axial stress | 20 | 3 psi |
40 plus axial stress | 27 | 4 psi |
50 plus axial stress | 33 | 5 psi |
100 plus axial stress or more | 67 or more | 10 psi max |
1. Allowable shear stress may be increased by addition of 10% of the axial stress due to the weight of the wall directly above.