§ 52.29 FIRE SYSTEMS.
   (A)   An approved double check detector assembly shall be the minimum protection on all new fire sprinkler systems using piping material that is not approved for potable water use and/or that does not provide for periodic flow-through. A reduced pressure principle detector assembly must be installed if any solution other than potable water can be introduced into the sprinkler system. Retrofitting on fire sprinkler systems will be required in each of the following circumstances:
      (1)   Where improper maintenance has occurred;
      (2)   On all high hazard systems;
      (3)   Wherever a specialist deems necessary; and
      (4)   Wherever required by the OAR.
   (B)   In the event an assembly is installed on a designated lateral, a detector assembly commensurate with the degree of hazard will be required.
(Ord. 620, passed 10-7-2009)