The following standards shall be used with the International Building Code and the International Residential Code:
(A) Acceptable wind load design procedure: 2012 IBC - Basic Wind Speed: The ultimate design wind speed shall be 120 mph, in risk category II, III and IV. 2012 IRC - Basic Wind Speed shall be 90 mph, Exposure C only;
(B) Ground snow load: 30 pounds per square foot;
(C) Frost depth: 36-inch minimum;
(D) Seismic design Category A, Site Class D; and
(E) Table R301.5 of the IRC shall reflect live loads for sleeping rooms of 40 pounds per square foot.